6. Space required for unit installation and operation

1

In case of single installation

Secure enough space around the unit as shown in the figure below.

[Fig. 6.0.1]

(1) If the distance is 300 mm [11-13/16 in] or more between the rear side and

the wall

<A> Top view

(Unit: mm [in])

15*

15*

450*

300*

A

[11-13/16]

[17-23/32]

[19/32]

[19/32]

(2) If the distance is 100 mm [3-15/16 in] or more between the rear side and

the wall

<A> Top view

(Unit: mm [in])

100*

450*

50*

50*

A

[3-15/16]

[17-23/32]

[1-31/32]

[1-31/32]

(3) If the wall height (H) of the front, rear or side exceeds the wall height

restriction

<B> Side view

(Unit: mm [in])

A

B

500

H

h

h

H

[19-11/16]

When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defined here, add the height that exceeds the height
limit <h> to the figures that are marked with an asterisk (*).

<Wall height limit> Front: Up to the unit height

Back: Up to 500mm [19-11/16 in] from the unit bottom
Side: Up to the unit height

(4) If there are obstacles at the upper part of the unit

<C> When there is little space up to an obstruction

(Unit: mm [in])

240

[9-15/32]

[1-31/32]

[39-3/8]

45

°

A

D

C

50

1000

A

Front

B

Unit height

C

Back

D

Air outlet guide (field-supplied)

(Unit: mm [in])

30

450*

300*

C

B

B

C

A

[11-13/16]

[17-23/32]

[1-3/16]

100

450*

100*

B

B

C

C

A

[3-15/16]

[17-23/32]

[3-15/16]

100*

C

C

B

A

A

A

B

450*

450

450

[17-23/32] [17-23/32] [17-23/32] [3-15/16]

15*

C

A

A

A

450

450

[17-23/32] [17-23/32]

[19/32]

900

300*

300*

B

B

C

C

A

[35-7/16]

[11-13/16]

[11-13/16]

1000*

900

300*

B

B

C

A

[11-13/16]

[35-7/16]

[39-3/8]

A

Front

B

Must be open

C

Wall height (H)

When multiple units are installed adjacent to each other, secure enough space
to allow for air circulation and walkway between groups of units as shown in
the figures.

At least two sides must be left open.

As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk (*).

2

In case of collective installation and continuous installation

[Fig. 6.0.2]

Summary of Contents for City Multi PUHY-P-THMU-A

Page 1: ...ATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte For use with R410A ...

Page 2: ...and fire may result Securely install the outdoor unit terminal cover panel If the terminal cover panel is not installed properly dust or water may enter the outdoor unit and fire or electric shock may result When installing and moving the air conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mix...

Page 3: ...ping made of phosphorus deoxidized copper and cop per alloy seamless pipes and tubes In addition be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur oxides dust dirt shaving particles oils moisture or any other contami nant Contaminants on the inside of the refrigerant piping may cause the refriger ant oil to deteriorate Store the piping to be used during...

Page 4: ... P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P72YHMU A BS PUHY P72YHMU A BS PUHY P72YHMU A BS PUHY P96YHMU A BS PUHY P120YHMU A BS PUHY P144 to P360YSHMU A BS require Twinning Kit to connect component unit modules in the field 5 Parts included list Unit mm in 1 The total indoor capacity of units run simultaneo...

Page 5: ... Up to the unit height Back Up to 500mm 19 11 16 in from the unit bottom Side Up to the unit height 4 If there are obstacles at the upper part of the unit C When there is little space up to an obstruction Unit mm in 240 9 15 32 1 31 32 39 3 8 45 A D C 50 1000 A Front B Unit height C Back D Air outlet guide field supplied Unit mm in 30 450 300 C B B C A 11 13 16 17 23 32 1 3 16 100 450 100 B B C C ...

Page 6: ...ecessary so that it does not move to the side and support it at 4 points If the unit is installed or suspended with 3 point support the unit may become unstable and fall 8m 26ft 8m 26ft 40 Fix unit tightly with bolts so that unit will not fall down due to earthquakes or strong winds Use concrete base or an angle bracket as the foundation of unit Vibration may be transmitted to the installation sec...

Page 7: ...led information on refrigerant piping system 2 Always observe the restrictions on the refrigerant piping such as rated length height difference and piping diameter to prevent equipment failure or a de cline in heating cooling performance 3 Branching cannot be made after header branching corresponding parts are marked with in the diagram below To the outdoor unit To the outdoor unit CAP 4 Do not in...

Page 8: ...ne in conventional refrigerant and refrigerant oil in the existing piping will cause the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Do not use a charging cylinder Using a charging cyl...

Page 9: ... 4 ø22 2 7 8 ø22 2 7 8 Liquid pipe ø19 05 3 4 ø19 05 3 4 ø19 05 3 4 ø19 05 3 4 ø19 05 3 4 Gas pipe ø34 93 1 3 8 ø34 93 1 3 8 ø34 93 1 3 8 ø34 93 1 3 8 ø34 93 1 3 8 A2 3 A3 3 1 ø12 7 for over 90m 295 ft 2 ø12 7 for over 40m 131 ft 3 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes for the models listed in the unit 1 2 and 3 columns When the order of the models for uni...

Page 10: ...frigerant line Use the table below as a guide for calculating the amount of additional charg ing and then charge the system accordingly If the calculation results in a fraction of less than 0 1 kg 4 oz round up to the next 0 1 kg 4 oz For example if the result of the calculation was 11 38 kg 402 oz round the result up to 11 4 kg 404 oz Additional Charge Additional refrigerant charge kg oz 10 Addit...

Page 11: ...r completing the operation D Pinched connecting pipe severing portion E Pinched connecting pipe brazing portion Refrigerant piping connection examples Fig 10 2 2 A Front pipe routing B Bottom pipe routing C Included with outdoor unit A Gas pipe field supply required B Liquid pipe field supply required C Shape Warning The section of the pipe on the unit between the two refrigerant service valves is...

Page 12: ...rigerant charge by using the formula and charge refrigerant additionally through the service port after completing piping connection work After completing work tighten the service port and cap securely so as not to generate any gas leakage Refer to the table on the below for appropriate tightening torque Restriction If a flammable gas or air oxygen is used as the pressurization gas it may catch fi...

Page 13: ... Pay special attention to insulation work in the ceiling plenum Fig 10 4 1 C A B D E A Steel wire B Piping C Oily mastic asphalt or asphalt D Heat insulation material A E Outer covering B Note When using polyethylene cover as covering material asphalt roofing shall not be required No heat insulation must be provided for electric wires Fig 10 4 2 B A D C E E E D A B A Liquid pipe B Gas pipe C Elect...

Page 14: ...nection does not allow the system to operate 8 When connecting a System Controller to outdoor units or performing a group operation of indoor units that are connected to different outdoor units a transmission line for centralized control is required When using a transmission line for centralized control connect the transmission line non polar 2 core wire to all TB7 terminals between all outdoor un...

Page 15: ...a possibility of small animal s entering the unit 11 3 Wiring transmission cables 1 Types of control cables 1 Wiring transmission cables Types of transmission cables Shielding wire CVVS CPEVS or MVVS Cable diameter More than 1 25 mm2 AWG 16 Maximum wiring length Within 200 m 656 ft Maximum length of transmission lines for centralized control and indoor outdoor transmission lines Maximum length via...

Page 16: ... CN40 2 If a system controller is used set SW2 1 on all of the outdoor units to ON Fig 11 3 2 MA Remote Controller 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to CN40 2 If a system controller is used set SW2 1 on all of the outdoor units to ON A Chan...

Page 17: ...or more Max transmission cable length M NET cable L1 and L3 L4 and L6 and L2 L6 200 m 656 ft 1 25 mm2 AWG 16 or more Remote controller cable length c1 c2 and c1 c2 c3 c4 200 m 656 ft 0 3 to 1 25 mm2 AWG 22 to 16 3 Transmission booster Fig 11 3 3 Max transmission cable length M NET cable 1 L1 L2 L3 L5 L6 200 m 656 ft 1 25 mm2 AWG 16 2 L1 L2 L3 L5 L7 200 m 656 ft 1 25 mm2 AWG 16 3 L1 L2 L4 200 m 656...

Page 18: ...A or 100 mA 0 1 sec or less 30 A 30 mA or 100 mA 0 1 sec or less 40 A 30 mA or 100 mA 0 1 sec or less 30 A 30 mA or 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 30 A 30 mA or 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 40 A 30 mA or 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 30 A 30 mA or 100 mA 0 1 sec or less 30 A 30 mA...

Page 19: ...4YSHMU A BS PUHY P72YHMU A BS PUHY P72YHMU A BS PUHY P120YHMU A BS PUHY P288YSHMU A BS PUHY P96YHMU A BS PUHY P72YHMU A BS PUHY P120YHMU A BS PUHY P312YSHMU A BS PUHY P120YHMU A BS PUHY P72YHMU A BS PUHY P120YHMU A BS PUHY P336YSHMU A BS PUHY P120YHMU A BS PUHY P96YHMU A BS PUHY P120YHMU A BS PUHY P360YSHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS Indoor unit 15 A 30 mA or 100 mA 0 1 sec or less...

Page 20: ...of the refrigerant circuit operating properly Unstable flow of the refrigerant emits a sound This is temporary and does not imply a problem The LEV is slightly open for preventing any refrigerant inside of the indoor unit that is not performing the heating operation from being liquefied This does not imply a problem 13 Rating plate information Model PUHY P72THMU A BS PUHY P96THMU A BS PUHY P120THM...

Page 21: ...0A 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 11 5 kg 25 LBS 6 oz Allowable pressure Ps 4 15 MPa 601 psi LP 2 21 MPa 320 psi Net weight 260 kg 573 LBS 5 oz 215 kg 473 LBS 16 oz 260 kg 573 LBS 5 oz 215 kg 473 LBS 16 oz 260 kg 573 LBS 5 oz 260 kg 573 LBS 5 oz Model PUHY P264YSHMU A BS PUHY P288YSHMU A BS Unit combination PUHY P120YHMU A BS PUH...

Page 22: ...panneau n est pas installé correctement la poussière ou l eau peut pénétrer dans l unité extérieure et un incendie ou un choc électrique peut en résulter En installant et en déplaçant le climatiseur vers un autre site ne le chargez pas avec un frigorigène différent de celui qui est spéci é sur l unité Si un autre frigorigène ou de l air est mélangé au frigorigène original le cycle frigori que peut...

Page 23: ...ez vous que les surfaces intérieures et extérieures des tuyaux sont propres et dépourvues de soufre d oxydes de poussières saletés de particules de rasage d huile d humidité ou de n importe quel autre contaminant dangereux Les contaminants à l intérieur de la tuyauterie du frigorigène peuvent détériorer l huile du frigorigène Entreposez à l intérieur la tuyauterie à utiliser pour l installation et...

Page 24: ... P192TSHMU A BS PUHY P216TSHMU A BS PUHY P240TSHMU A BS PUHY P72YHMU A BS PUHY P96YHMU A BS PUHY P120YHMU A BS PUHY P144YSHMU A BS PUHY P168YSHMU A BS PUHY P192YSHMU A BS PUHY P216YSHMU A BS PUHY P240YSHMU A BS Niveau de bruit 60 Hz 58dB A 58dB A 60dB A 61dB A 61dB A 62 5dB A 62 5dB A 63dB A Pression statique externe 0 Pa 2 Unités d intérieur Capacité totale 50 130 1 Modèle 06 96 Quantité 1 15 1 2...

Page 25: ...vant Jusqu à la hauteur de l appareil Dos Jusqu à 500 mm 19 11 16 in du fond de l appareil Côté Jusqu à la hauteur de l appareil 4 S il y a des obstacles à la partie supérieure de l unité C Quand il y a peu d espace jusqu à une obstruction Unité mm in 240 9 15 32 1 31 32 39 3 8 45 50 1000 A Avant B Hauteur de l unité C Dos D Guide de sortie d air fourni sur le terrain 2 En cas d installation colle...

Page 26: ...vents forts Utilisez du support en béton ou une cornière d assemblage comme fondation de l unité Des vibrations peuvent être transmises à la section d installation et bruit et vibration peuvent être produits par le plancher et les murs selon les conditions d installation Fournissez par conséquent une protection suf sante contre les vibrations coussinets cadre de coussin etc Construisez les fondati...

Page 27: ...connectée qu un essai d étanchéité du frigorigène ait été exécuté et que le processus d évacuation ait été complété c N utilisez jamais de frigorigène pour exécuter une purge d air Servez vous toujours d une pompe à vide pour évacuer d Soyez sûr de charger le système avec un frigorigène liquide e Un manque ou un excès de frigorigène provoque un arrêt d urgence de l unité Chargez le système d une q...

Page 28: ... de récupération du frigorigène Le mélange de frigorigène conventionnel et d huile réfrigérant peut détériorer l huile réfrigérante Le mélange d eau détériore l huile réfrigérante Le frigorigène R410A ne contient aucun chlore Par conséquent les détecteurs de fuite de gaz pour les frigorigènes conventionnels ne réagissent pas Gérez les outils utilisés pour le R410A plus soigneusement que d habitude...

Page 29: ...s dans les colonnes 1 2 et 3 Lorsque l ordre des modèles change veillez à utiliser la taille de tuyau appropriée B C D Unité mm in Capacité totale d unités d intérieur Tube de uide Tube de gaz Total de modèle d unité en aval Joint 54 ø9 52 3 8 ø15 88 5 8 72 CMY Y102S G2 55 72 ø9 52 3 8 ø19 05 3 4 73 144 CMY Y102S L2 73 108 ø9 52 3 8 ø22 2 7 8 145 240 CMY Y202 G2 109 144 ø12 7 1 2 ø28 58 1 1 8 La 1...

Page 30: ...m ft 3 1 oz ft m 0 2 kg m ft 2 15 oz ft m 0 12 kg m ft 1 29 oz ft Taille de tube de uide Longueur totale de ø9 52 mm 3 8 in Taille de tube de uide Longueur totale de ø6 35 mm 1 4 in D m 0 06 kg m ft 0 65 oz ft m 0 024 kg m ft 0 26 oz ft Exemple Intérieur 1 48 A ø12 7 mm 1 2 in 40 m 131 ft a ø9 52 mm 3 8 in 10 m 32 ft 2 36 B ø9 52 mm 3 8 in 10 m 32 ft b ø9 52 mm 3 8 in 5 m 16 ft 3 15 C ø9 52 mm 3 8...

Page 31: ...alves haute et basse pression pour empêcher la fuite de gaz Prenez les mesures suivantes 1 à 4 pour retirer le tube de connexion rétréci avant de connecter les tubes de frigorigène à l unité extérieure 1 Véri ez que la valve de frigorigène est complètement fermée tournée à fond dans le sens horaire 2 Branchez un tube de remplissage au port de service sur la valve basse pression haute pression et e...

Page 32: ...rès le test d herméticité éliminez l agent de barbotage Si un gaz in ammable ou l air oxygène est utilisé comme gaz de pressurisation il peut s en ammer ou exploser 2 Pressurisation avec un gaz réfrigérant et de l azote 1 Après une première pressurisation du frigorigène liquide R410A en gaz de pression d environ 0 2 MPa 29 psi pressurisez à la pression nominale de 4 15 MPa 602 psi avec de l azote ...

Page 33: ...u pourrait avoir pénétré Appliquez une pression d azote sec jusqu à 0 05 MPa 7 25 psi et appliquez de nouveau le vide Pour nir scellez avec le frigorigène liquide à travers le tube de uide et ajustez la tuyauterie de gaz pour obtenir une quantité appropriée de frigorigène pendant le fonctionnement N exécutez jamais de purge d air à l aide du frigorigène Remarque Ajoutez toujours une quantité appro...

Page 34: ...et emplacement pour le raccordement des câbles 1 Unité extérieure 1 Retirez le panneau avant du boîtier de commande en retirant les 4 vis et en le poussant légèrement vers le haut avant de le sortir 2 Connectez la ligne de transmission intérieur extérieur au bloc de jonction TB3 Si plusieurs appareils extérieurs sont connectés au sein du même système frigori que connectez en série TB3 borne M1 M2 ...

Page 35: ...ieur longueur maximale par l intermédiaire des unités extérieures 500 m 1 640 ft maximum La longueur maximale du câblage entre le bloc d alimentation pour des lignes de transmission sur les lignes de transmission pour la commande centralisée et chaque appareil extérieur et contrôleur de système est de 200 m 656 ft 2 Câbles de la télécommande Télécommande M NET Type de câble de télécommande Câble e...

Page 36: ... un contrôleur de système est utilisé réglez SW2 1 sur tous les appareils extérieurs sur ON marche Fig 11 3 2 Télécommande MA A Changez le cavalier de CN41 à CN40 1 B SW2 1 ON marche 2 C Laissez le cavalier sur CN41 B SW2 1 ON marche 2 1 Quand l alimentation n est pas connectée à la ligne de transmission pour la commande centralisée débranchez le connecteur mâle de l alimentation CN41 sur UN appar...

Page 37: ... principale au sein du même groupe plus 100 M NET R C secondaire 151 à 200 Réglez sur une adresse IC principale au sein du même groupe plus 150 MA R C Dé nition inutile d adresse dé nition principale secondaire nécessaire 1 OC OS1 et OS2 des appareils extérieurs dans le même système frigori que sont automatiquement identi és Ils sont identi és comme OC OS1 et OS2 dans l ordre décroissant de capaci...

Page 38: ...HMU A BS PUHY P120THMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 mA 0 1 sec ou moins 43 6 PUHY P96THMU A BS 13 3 6 13 3 6 40 40 40 40 A 30 mA ou 100 mA 0 1 sec ou moins 36 3 PUHY P240TSHMU A BS PUHY P120THMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 mA 0 1 sec ou moins 43 6 PUHY P120THMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 mA 0 1 sec ou moins 43 6 PUHY P264TSHMU A BS PUHY P120THMU A BS 13 3 6 13 3 6 50 50 ...

Page 39: ...P336YSHMU A BS PUHY P120YHMU A BS 5 3 10 5 3 10 25 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 19 6 PUHY P120YHMU A BS 5 3 10 5 3 10 25 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 19 6 PUHY P96YHMU A BS 3 3 12 3 3 12 20 20 20 20 A 30 mA ou 100 mA 0 1 sec ou moins 16 4 PUHY P360YSHMU A BS PUHY P120YHMU A BS 5 3 10 5 3 10 25 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 19 6 PUHY P120YHMU A BS 5 3 10 ...

Page 40: ...dique que le circuit du frigorigène fonctionnement correctement Immédiatement après la mise en route l unité intérieure émet le bruit de l écoulement du frigorigène Af chage normal L écoulement instable du frigorigène émet un bruit Ceci est provisoire et n indique pas un problème De l air chaud provient d une unité intérieure qui n exécute pas de chauffage Af chage normal Le LEV est légèrement ouv...

Page 41: ...UHY P264YSHMU A BS PUHY P288YSHMU A BS Unité combinée PUHY P120YHMU A BS PUHY P72YHMU A BS PUHY P72YHMU A BS PUHY P120YHMU A BS PUHY P96YHMU A BS PUHY P72YHMU A BS Frigorigène R410A 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz 9 0 kg 19 LBS 13 oz Pression autorisée Ps 4 15 MPa 601 psi LP 2 21 MPa 320 psi Poids net 260 kg 573 LBS 5 oz 215 kg 47...

Page 42: ......

Page 43: ......

Page 44: ...I CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment ...

Reviews: