Job Name:
Location:
Drawing Reference:
Schedule No.
System No.:
Date:
• R410A refrigerant
• Seven sizes from 6,000 to 30,000 Btu/h
• Powerful airflow (CFM)
• Compact, lightweight, shiny-white, flat-panel design
• Quiet operation
• Multiple fan-speed settings
• Intake grille filter is easily removed for cleaning
• Built-in receiver is standard
Model:
PKFY-P24NKMU-E2
GENERAL FEATURES
SPECIFICATIONS
Capacity*
Cooling……………………………………………....24,000 Btu/h
Heating……………………………………………....27,000 Btu/h
Power
Power Source………………..........208 / 230V, 1-phase, 60Hz
Power Consumption
Cooling…………………………………………….………0.07 kW
Heating…………………………………………….………0.07 kW
Current
Cooling……...................................................……………0.50 A
Heating……...................................................……………0.50 A
Minimum Circuit Ampacity (MCA)……………….…..……...0.63 A
Maximum Overcurrent Protection (MOCP) Fuse..….......…..15 A
External Finish
……………...….………Munsell No. 1.0Y 9.2 / 0.2
External Dimensions
Inches………………………..14-3/8 H x 46-1/16 W x 11-5/8 D
mm…………………………………….365 H x 1,170 W x 295 D
Net Weight
Unit………………..…...……………..................46 lbs. / 21 kg
Coil Type
………………...........................................….Cross Fin
(Aluminum Plate Fin and Copper Tube)
Fan
Type x Quantity………………..…………...Line Flow Fan x 1
Airflow Rate (Low-High)...…….…….…………...570 - 920 CFM
Motor
Type………..………..………..………..Direct-drive DC Motor
Output………..………..………..………..………..….0.056 kW
Air Filter
..…………………………….Polypropylene Honeycomb
Refrigerant Piping Dimensions
Liquid (High Pressure)……............…3/8" / 9.52 mm (Flare)
Gas (Low Pressure)………………..…5/8" / 15.88 mm (Flare)
Drainpipe Dimension
……............……...…….I.D. 5/8" / 16 mm
Sound Pressure Levels
Low-High….…………….………….……………39 - 49 dB(A)
OPTIONS
□ External Heat Adapter……………………….…PAC-YU25HT
* Cooling / Heating capacity indicated at the maximum value at
operation under the following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F
(35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB
Note:
Ventilation air: Providing sufficient ventilation air is an impor-
tant part of every building design. ASHRAE Standard 62 provides
the minimum ventilation air requirement. Also, check local codes.
Notes:
• IT Terminal plug