25
Control modes
Control details
3. Drain pump
Except for
PKFY-P06NAMU-E
PKFY-P08NAMU-E
1. Thermoregulating
function
Remarks
2. Fan
4. Vane
(up/ down vane change)
Same control as COOL operation
Same control as COOL operation
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermoregulating signal and the
room temperature (TH1).
Dry thermo ON Room temperature
desired tempe 2 °F
Dry thermo OFF Room temperature
desired temperature
1-2. Frozen prevention control
No control function
Indoor fan operation controlled depends on the compressor conditions.
Room
temperature
3 min. passed since starting operation
Thermoregulating signal Room temperature (T1)
Dry thermo
ON
time (min)
Dry thermo
OFF
time (min)
Less than 64 °F
Over 64 °F
ON
OFF
T1
83 °F
83°F > T1
79 °F
79°F > T1
75 °F
75°F > T1
Unconditional
9
3
7
3
5
3
3
3
10
3
Dry thermo OFF
Note: Remote controller setting is not acceptable.
Dry thermo
Fan speed notch
ON
OFF
[Low]
Stop
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
°F°C
°F°C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
8-2. DRY OPERATION
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display DRY.
3
Press the TEMP. button to set the desired temperature.
NOTE
: The set temperature changes 2°F when the or button is
pressed one time. Dry 67 to 87°F.