24
GB
In case of collective installation and continuous installation
• When installing multiple units, make sure to take into consideration factors such as providing enough space for people to pass through, ample
space between blocks of units, and sufficient space for airflow. (The areas marked with [A] in the figures below must be left open.)
• In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to
L1, L2, and L3 as shown in the tables below.
• If there are walls in the front and rear of the block of units, up to six units (three units for units P168, EP168, and EP192) can be installed
consecutively side by side, and a space of 1000 mm (39-3/8 in) or more must be left between each block of six units (three units for unit P168,
EP168, and EP192).
(1) Side-by-side installation
(2) Face-to-face installation
(3) Combination of face-to-face and side-by-side installations
[A]: Leave open in two directions.
[mm (in)]
When the distances between the units (L4)
need to be small
When the distance behind the block of units
(L2) needs to be small
Required minimum distance [mm (in)]
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L4 (Between)
L1 (Front)
L2 (Rear)
L4 (Between)
450 (17-3/4) +h1
450 (17-3/4) +h2
30 (1-3/16)
450 (17-3/4) +h1
300 (11-13/16) + h2
450 (17-3/4)
When there are walls in the front and rear of
the block of units
When there is a wall on either the right or left
side of the block of units
Required minimum distance [mm (in)]
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L4 (Between)
L3 (Right/Left)
L4 (Between)
450 (17-3/4) +h1
300 (11-13/16) + h2
450 (17-3/4)
30 (1-3/16) + h3
450 (17-3/4)
When there are walls in the front and rear of
the block of units
When there are two walls in an L-shape
Required minimum distance [mm (in)]
Required minimum distance [mm (in)]
L2 (Rear)
L2’ (Rear)
L4 (Between)
L2 (Rear)
L3 (Right/Left)
L4 (Between)
450 (17-3/4) +h2
450 (17-3/4) +h2’
900 (35-7/16)
450 (17-3/4)
1000 (39-3/8) + h3
900 (35-7/16)
[A]
[A]
h2
L2
L1
h1
L4
Unit height
Unit height
[A]
[A]
h2
h1
L1
L2
L4
Unit height
Unit height
[A]
[A]
h1
h2
L1
L4
L4
L2
Unit height
Unit height
h3
L4
L3
L4
Unit height
h2
L2’
L4
L2
h2’
[A]
[A]
Unit height
Unit height
[A]
[A]
h2
L2
L4
L3
h3
Unit height
Unit height
WT09190X01.book 24 ページ 2018年11月29日 木曜日 午前8時59分