Mitsubishi Electric Air Conditioner CITY MULTI

 

CMY-ER100CBK 

Twinning Kit Installation Manual

s

 For your safety, thoroughly read the following instructions prior to installation.

Safety Precautions

s

 Thoroughly read the following “Safety Precautions” to ensure proper installation.

s

 Observe the following important safety precautions at all times.

s

 Hazards that can occur from incorrect handling are classified by the symbols below:

WARNING

CAUTION

Incorrect handling can result in death or serious injury.

Incorrect handling can result in bodily injury and/or structure damage.

WARNING

CAUTION

Only a dealer or qualified technician should 
perform installation.

Properly install all parts according to the 
instructions in the Installation Manual.

After installation, check for a refrigerant leak.

Do not make any modifications or alterations.
Consult your dealer for repair.

When installing or relocating the unit, check that 
no substance other than the specified refrigerant 
(R410A) enters the refrigerant circuit.

Do not touch the refrigerant pipes and refrigerant 
circuit components with bare hands during and 
immediately after operation.

In the event of a refrigerant leak, thoroughly 
ventilate the room.

s

 Improper installation may result in refrigerant gas leakage and 

equipment damage.

s

 If the wrong twinning pipe or wrong size connecting pipe is used, 

air conditioning performance will suffer.

s

 If leaked refrigerant comes in contact with a heat source, such 

as a fan heater, stove, or electric grill, toxic gases will be  
generated.

s

 Improper installation may result in water leakage, electric shock, 

or fire.

s

 Any presence of foreign substance or air can cause abnormal 

pressure rise or explosion.

s

 During or immediately after operation, certain parts of the unit 

such as pipes and compressor may be either very cold or hot, 
depending on the state of the refrigerant in the unit at the time. 
To reduce the risk of frostbites and burns, do not touch these 
parts with bare hands.

s

 If refrigerant leaks and comes in contact with an open flame, 

toxic gases will be generated.

Properly dispose of packing materials.

s

 Plastic bags can pose suffocation and choking hazards: keep 

them out of the reach of children. Tear the plastics bags before 
disposing of them.

* See the Installation Manual that came with the outdoor unit for installation instructions.

WT07685X01

Summary of Contents for CITY MULTI CMY-ER100CBK

Page 1: ...ents with bare hands during and immediately after operation In the event of a refrigerant leak thoroughly ventilate the room s Improper installation may result in refrigerant gas leakage and equipment damage s If the wrong twinning pipe or wrong size connecting pipe is used air conditioning performance will suffer s If leaked refrigerant comes in contact with a heat source such as a fan heater sto...

Page 2: ...llowing items are included with the Twinning Kit CMY ER100CBK Verify that all items are present before starting installation Always use the twinning pipes included in the kit when preparing the twinning kit If the field supplied pipes do not fit the parts in the kit use the accessory piping parts listed below 1 Package contents Model 1 Low pressure twinning kit 2 High pressure twinning pipe 3 Fixing...

Page 3: ... it to item 1 low pressure twinning kit 4 Braze item 4 elbow pipe to the low pressure pipe in the middle 5 Wrap the pipe in front of item 1 low pressure twinning kit with item 8 pipe cover and attach compressor cables to item 8 pipe cover with item e cable tie to keep them out of direct contact with the pipes 5 Slope of twinning pipes high pressure side only Make sure the slope of the twinning pip...

Page 4: ...lation covers can shrink Overlap the tape as shown in the left figure so that there will be no gap in between the insulation cover or field installed insulation material 6 The length of the straight pipe between indoor units and the twinning pipe high pressure pipe Use the pipes supplied in the twinning kit and make sure the section of the field supplied pipe that connects to the twinning pipe has at...