6 Parameter Setting
6.3 Changing the IO-Link Module Parameters
51
6
6.3
Changing the IO-Link Module Parameters
This section describes the procedure for changing the parameter.
The precautions for changing the parameter are the same as those in the following section.
Setting via the engineering tool
Changing the network configuration
When changing the network configuration diverting the created project, set the parameter in the following procedure.
1.
Power off the module.
2.
Connect the modules again according to the desired network configuration.
3.
Power on the module.
4.
Open the "CC IE Field Configuration" window.
For the master/local module RJ71GF11-T2
[Navigation window]
[Parameter]
[Module Information]
[RJ71GF11-T2]
[Module Parameter]
[Basic Settings]
[Network Configuration Settings]
5.
Drag and drop a module to set the IO-Link module. Input a numerical value to set the station number of the station.
Change the value as necessary.