Network Management
Functions
MELSEC-L Series – CANopen
Module ME3CAN1-L
4 – 45
Object 1F89
H
: Boot time
The boot time defines the time out in ms for the NMT slave boot-up. The time is measured from the
start of the NMT slave boot process until the signaling of successful boot of all mandatory NMT slaves.
If the boot time elapses before all mandatory slaves are started, the NMT start-up will be stopped and
the NMT start-up master will be disabled.
The value 0 disables the timer.
Setting range: K0 to K4, 294, 967, 295.
Object 102A
H
: NMT inhibit time
This object configures the minimum time between two NMT messages. The 16 bit value is given in
multiples of 100 μs (lowest counting resolution of ME3CAN1-L: 1ms).
The value 0 disables the inhibit time.
Setting range: In the ME3CAN1-L, the value is fixed to 0.
Mandatory
How shall the CANopen
device be present prior
to network start-up?
Bit = 0: May be present (CANopen
device is
optional).
Bit = 1: Shall be present (CANopen
device is
mandatory).
앫
For mandatory slaves, please consider the bit 4
and 6 of the object 1F80
H
앫
For LSS slave, this bit must be set to 1 to enable
the LSS service for this NMT slave. (Refer to sec-
tion 4.8.11)
Reset
communication
How shall the NMT service
Reset communication
be executed for the CANopen
device?
Bit = 0: May be executed at any time.
Bit = 1: Shall not be executed when the
CANopen
device is in NMT state
Operational
.
앫
When using flying master service, all nodes
reset communication command will be exe-
cuted during the flying master negotiation.
앫
If heartbeat consumption is not configured for
this node, the NMT start-up master will start
with node guarding, which must be answered
within 100ms.
앫
If heartbeat is not used or not supported,
please confirm that the NMT slave supports
node guarding.
앫
If the NMT slave is configured for life guarding
of the NMT master, take care that also the NMT
Master is configured for node guarding. Other-
wise the NMT slave will go into the NMT error
state.
앫
If no heartbeat or no node guarding confirma-
tion is received within the Heartbeat consum-
ing time after the Node Guarding RTR message,
the NMT slave start-up ends with an error.
Reserved
Set to 0, otherwise SDO access error 06090030
H
will occur.
—
Bit/Item
Description
Remark
Tab. 4-30:
Description of t
he configuration field
Summary of Contents for CANopen ME3CAN1-L
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ...IV ...
Page 18: ...Abbreviations and Generic Terms Overview MELSEC L Series CANopen Module ME3CAN1 L 1 4 ...
Page 22: ...System Configuration System Equipment 2 4 MITSUBISHI ELECTRIC ...
Page 162: ...Programming Layer 2 Communication 7 24 MITSUBISHI ELECTRIC Program Fig 7 24 Example Program 1 ...
Page 164: ...Programming Layer 2 Communication 7 26 MITSUBISHI ELECTRIC Fig 7 26 Example Program 3 ...
Page 166: ...Programming Layer 2 Communication 7 28 MITSUBISHI ELECTRIC Fig 7 28 Example Program 5 ...
Page 178: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 40 ...
Page 184: ...Troubleshooting Error Code and Error Message Summary 8 6 MITSUBISHI ELECTRIC ...
Page 187: ......