The bridge module occupies 1 to 4 stations starting the station number specified in the CC-Link system.
For details on buffer memory areas of the master module, refer to the user's manual for the master module used.
6.1
Lists of Remote I/O Signals
When the CC-Link operation mode is Ver.1.10
The following table lists remote I/O signals when the CC-Link operation mode is Ver.1.10.
Remote I/O signals when 1 station is occupied
Both remote input (RX) and remote output (RY) of the bridge module use 32 points.
n: Address assigned to the master station in the station number setting
Signal direction: Bridge module
master module
Signal direction: Master module
bridge module
Remote input (RX)
Name
Remote output (RY)
Name
RXn0
Use prohibited
RYn0
Use prohibited
RXn1
DP/DN short error
RYn1
Automatic address detection
command
RXn2
Use prohibited
RYn2 to RYnF
Use prohibited
RXn3
Transmission cable voltage drop
error
RXn4
DP/DN disconnection error
RXn5
Use prohibited
RXn6 to RXnF
Latest error ID simple information
RX(n+1)0
Slave module alarm signal
RY(n+1)0 to RY(n+1)9
RX(n+1)1 to RX(n+1)3
Use prohibited
RX(n+1)4
Automatic address detection flag
RX(n+1)5 to RX(n+1)9
Use prohibited
RX(n+1)A
Error status flag
RY(n+1)A
Error reset request flag
RX(n+1)B
Remote READY
RY(n+1)B to RY(n+1)F
Use prohibited
RX(n+1)C to RX(n+1)F
Use prohibited