7 FUNCTIONS
7.8 Input/output Hold/Clear Setting Function
67
7
7.8
Input/output Hold/Clear Setting Function
This function sets to hold or clear the last input or output values when the NZ2AW1GNAL is disconnected from a data link,
when the operating status of the CPU module is in STOP state, or when the operating status of the CPU module is in error
stop status.
If a moderate or major error occurs in the NZ2AW1GNAL, I/O will be turned off regardless of the input/output
hold/clear settings.
Input/output hold/clear settings and operation
The following table lists the setting items.
■
Output data hold/clear setting
The output of the NZ2AW1GNAL operates as follows depending on the setting value of "Output data hold/clear setting".
■
Word input data hold/clear setting when disconnected
The value of the link device (RX, RWr) operates as follows depending on the setting value of "Word input data hold/clear
setting when disconnected".
Setting method
For the input/output hold/clear setting function, from the CC-Link IE TSN configuration window, set "Output data hold/clear
setting" and "Word input data hold/clear setting when disconnected" in the "Parameter of Slave Station" window. (
Item
Description
Output data hold/clear setting
Sets whether to clear or hold the output to the slave module when the NZ2AW1GNAL is disconnected
from the CC-Link IE TSN data link or a CPU module stop error occurs.
Word input data hold/clear setting when
disconnected
Sets whether to clear or hold the word input data when the word slave module is disconnected.
Operating status
Output status of bit output
Output status of word output
NZ2AW1GNAL
CPU module
Output data hold/
clear setting:
CLEAR
Output data hold/
clear setting: HOLD
Output data hold/
clear setting: CLEAR
Output data hold/
clear setting: HOLD
During data link
RUN
Outputs bit output value
(RY value)
Outputs bit output value
(RY value)
Outputs word output value
(RWw value)
Outputs word output
value (RWw value)
STOP
Off
Hold
0
Hold
PAUSE
Outputs bit output value
(RY value)
Outputs bit output value
(RY value)
Outputs word output value
(RWw value)
Outputs word output
value (RWw value)
RESET
Off
Hold
0
Hold
Error stop
Off
Hold
0
Hold
Disconnected/cyclic
transmission stopped
Off
Hold
0
Hold
Operating status
Link device input value
Word input data hold/clear setting
when disconnected: CLEAR
Word input data hold/clear setting
when disconnected: HOLD
Normal operation
Bit slave module
Input value stored in RX
Input value stored in RX
Word slave module
Input value is stored in RWr
Input value is stored in RWr
Slave module disconnection
Bit slave module
0
0
Word slave module
0
Hold
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......