Appendix 3 Remote Buffer Memory
163
A
Parameter area initialization completion
■
Address
■
Description
This area indicates the initialization completion status of the parameter information stored in the non-volatile memory.
(1) 0: Not executed, 1: Completed
When the initialization of the parameter information is completed, b0 becomes 1: Completed. (The initial value is set to 0: Not
executed.)
For details, refer to the following.
Page 162 Parameter area initialization command
Slave parameter storage area
■
Address
■
Description
Parameters of each ID are stored in 1000H to 3FFFH.
The following table lists the assignment of the remote buffer memory addresses.
The first word of the 48 words indicates the ID, and the data is arranged in ascending order of ID in units of 48
words.
When adding a slave module or changing the ID, perform the automatic address detection function again.
Page 53 Automatic Address Detection Function
Name
Address
Parameter area initialization completion
0403H
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
0
(1)
Name
Address
Slave parameter storage area
1000H to 3FFFH
Address
Name
Details
1000H to 102FH
Parameter area 1st module (48 words)
The parameter area of each ID has 48 words and can
store information of up to 256 parameters.
1030H to 105FH
Parameter area 2nd module (48 words)
3FA0H to 3FCFH
Parameter area 255th module (48 words)
3FD0H to 3FFFH
Parameter area 256th module (48 words)
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......