Basic operation procedure (External operation)
90
4.3.5
Using an analog signal (current input) to give a
frequency command
POINT
POINT
• Switch ON the STF (STR) signal to give a start command.
• Turn ON the AU signal.
• Set
Pr.79 Operation mode selection
="2" (External operation mode).
[Connection diagram]
NOTE
• When both the forward rotation switch (STF) and the reverse rotation switch (STR) are ON, the motor cannot be started. If
both are turned ON while the inverter is running, the inverter decelerates to a stop.
•
Pr.184 AU terminal function selection
must be set to "4" (AU signal) (initial value).
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.184 AU terminal function selection
Operation example
Operate at 60 Hz.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Terminal 4 input selection
Turn ON the terminal 4 input selection signal (AU). Input to the terminal 4 is enabled.
3.
Start
Turn ON the start switch (STF or STR). [STF] or [STR] indicator is on.
4.
Acceleration
→
constant speed
Input 20 mA. The frequency value on the indication increases in
Pr.7 Acceleration time,
and "60.00 Hz" appears. [FWD]
indicator is on during the forward rotation, and [REV] indicator is on during the reverse rotation.
5.
Deceleration
Input 4 mA or less. The frequency value on the indication decreases in
Pr.8 Deceleration time,
and the motor stops rotating
with "0.00 Hz" displayed. [FWD] or [REV] indicator is OFF.
6.
Stop
Turn OFF the start switch (STF or STR). [STF] or [STR] indicator turns OFF.
Inverter
Switch
5(-)
4(+)
Forward rotation start
Reverse rotation start
STF
STR
SD
AU
Current signal
source
(4 to 20 mADC)