Basic operation procedure (PU operation)
83
4
4.2.2
Setting the frequency by switches (multi-speed
setting)
POINT
POINT
• Use the operation panel (
or
) to give a start command.
• Turn ON the RH, RM, or RL signal to give a frequency command. (multi-speed setting)
• Set
Pr.79 Operation mode selection
="4" (External/PU combination operation mode 2).
[Connection diagram]
NOTE
• The terminal RH is initially set to 60 Hz. The terminal RM is set to 30 Hz, and the RL is set to 10 Hz. (To change, set
Pr.4,
Pr.5, and Pr.6
.)
• In the initial setting, when two or more of multi-speed settings are simultaneously selected, priority is given to the set
frequency of the lower signal.
For example, when RH and RM signals turn ON, RM signal (
Pr.5
) has a higher priority.
• Maximum of 15-speed operation can be performed.
Parameters referred to
Pr.4 to Pr.6 (Multi-speed setting)
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.79 Operation mode selection
Operation example
Operate at a low-speed (10 Hz).
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Changing the operation mode
Set "4" in
Pr.79
. [PU+E] indicator is on.
3.
Setting the frequency
Turn ON the low-speed switch (RL).
4.
Start
→
acceleration
→
constant speed
Press
or
to start running. The frequency value on the indication increases in
Pr.7 Acceleration time
, and
"10.00 Hz" appears.
5.
Deceleration
→
stop
Press
to stop. The frequency value on the indication decreases in
Pr.8 Deceleration time,
and the motor stops
rotating with "0.00 Hz" displayed. Turn OFF the low-speed switch (RL).
Inverter
High speed
Middle speed
Low speed
SD
RH
RM
RL
Operation panel
Switch
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Time
RH
RM
RL