(M) Monitor display and monitor output signal
386
NOTE
• The output terminals that have not been assigned with a REM signal by
Pr.190 to Pr.196
do not turn ON/OFF even if "0 or 1"
is set in the terminal bits of
Pr.496 and Pr.497
. (ON/OFF is performed with the assigned functions.)
• When
Pr.495
= "1 or 11" (remote output data retention at power OFF), take measures such as connecting R1/L11 with P/+,
and S1/L21 with N/- so that the control power is retained. If the control power is not retained, the output signal after turning
ON the power is not guaranteed to work. When connecting the converter unit (FR-CC2), assign the instantaneous power
failure detection (X11) signal to an input terminal to input the IPF signal from the FR-CC2 to the terminal for X11 signal.
???????
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)
5.11.11
Analog remote output function
Analog remote output (Pr.656 to Pr.659)
• The terminals FM, AM and the analog output terminal of the option FR-A8AY can output the values set in
Pr.656
to
Pr.659
(Analog remote output)
.
• When
Pr.54 FM terminal function selection
= "87, 88, 89, or 90" (remote output), a pulse train can be output from the
terminal FM.
• For FM output (
Pr.291 Pulse train I/O selection
= "0 (initial value) or 1"):
Terminal FM output [pulses/s] = 1440[Hz]
(analog remote output value - 1000)/100
Where the output range is 0 to 2400 pulses/s.
• For high-speed pulse output (
Pr.291 Pulse train I/O selection
= "10, 11, 20, or 21"):
Terminal FM output [pulses/s] = 50K[Hz]
(analog remote output value - 1000)/100
Where the output range is 0 to 55k pulses/s.
An analog value can be output from the analog output terminal.
Pr.
Name
Initial
value
Setting
range
Description
655
M530
Analog remote
output selection
0
0
Remote output data is cleared when the
power supply is turned OFF
Remote output data is
cleared during an inverter
reset
1
Remote output data is retained when the
power supply is turned OFF
10
Remote output data is cleared when the
power supply is turned OFF
Remote output data is
retained during an inverter
reset
11
Remote output data is retained when the
power supply is turned OFF
656
M531
Analog remote
output 1
1000%
800 to
1200%
Value output from the terminal set as "87" in
terminal function selection
(Pr.54, Pr.158)
Set the analog value for
outputting from the analog
output terminals FM and AM
and option FR-A8AY.
657
M532
Analog remote
output 2
1000%
800 to
1200%
Value output from the terminal set as "88" in
terminal function selection
(Pr.54, Pr.158)
658
M533
Analog remote
output 3
1000%
800 to
1200%
Value output from the terminal set as "89" in
terminal function selection
(Pr.54, Pr.158)
659
M534
Analog remote
output 4
1000%
800 to
1200%
Value output from the terminal set as "90" in
terminal function selection
(Pr.54, Pr.158)
1440
1100
1200
Pulse speed
[pulse/s]
800
1000
Analog remote output value [%]
0
2400
Terminal FM (FM output)
50K
1100
1200
Pulse speed
[pulse/s]
800
1000
Analog remote output value [%]
0
55K
Terminal FM (High-speed pulse train output)