Installation of the inverter and enclosure design
26
Vibration, impact
The vibration resistance of the inverter is up to 5.9 m/s
2
(2.9 m/s
2
or less for the FR-A860-02890 or higher) at 10 to 55 Hz
frequency and 1 mm amplitude for the directions of X, Y, Z axes. Applying vibration and impacts for a long time may loosen
the structures and cause poor contacts of connectors, even if those vibration and impacts are within the specified values.
Especially when impacts are applied repeatedly, caution must be taken because such impacts may break the installation feet.
Countermeasure
• Provide the enclosure with rubber vibration isolators.
• Strengthen the structure to prevent the enclosure from resonance.
• Install the enclosure away from the sources of the vibration.
2.3.2
Amount of heat generated by the inverter
Regarding the amount of heat generated in the FR-A860 series inverter
The amount of heat generated by the FR-A860 series inverter is shown in the following tables.
NOTE
• The amount of heat generated shown assumes that the output current is inverter rated current, power supply voltage is 575
V, and carrier frequency is 2 kHz.
Voltage
Inverter model
Amount of heat generated (W)
SLD
LD
ND
HD
600 V class
FR-A860-00027
65
60
45
35
FR-A860-00061
115
105
75
55
FR-A860-00090
160
145
110
75
FR-A860-00170
270
250
185
140
FR-A860-00320
510
410
320
230
FR-A860-00450
680
610
480
340
FR-A860-00680
980
880
770
560
FR-A860-01080
1450
1300
1080
800
FR-A860-01440
2000
1800
1500
1200
FR-A860-01670
2400
2200
1800
1500
FR-A860-02430
3400
3100
2200
1800
FR-A860-02890
3600
3200
2600
1900
FR-A860-03360
4300
3900
3200
2400
FR-A860-04420
5500
5000
3700
2900