41
6 PARAMETER LIST
For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter's setting, change and check can be
made on the operation panel.
Notation
[E800]: Available for the standard model.
[E800-1]: Available for the FM type inverter (standard model).
[E800-4]: Available for the AM (50 Hz) type inverter (standard model).
[E800-5]: Available for the AM (60 Hz) type inverter (standard model).
[E800(-E)]: Available for the standard and Ethernet models.
[E800-(SC)E]: Available for the Ethernet model and the safety communication model.
[E800-SCE]: Available for the safety communication model.
[E800-(SC)EPA]: Available for the Protocol group A (Ethernet model / safety communication model).
[E800-(SC)EPB]: Available for the Protocol group B (Ethernet model / safety communication model).
[200/400 V class]: Available for the 200/400 V class inverters.
[575 V class]: Available for the 575 V class inverters.
[3-phase]: Available for the three-phase power input model.
CAUTION
l
indicates simple mode parameters. Use
Pr.160 User group read selection
to indicate the simple mode parameters only
(initial setting is to indicate the extended mode parameters).
l
The changing of the parameter settings may be restricted in some operating statuses. Use
Pr.77 Parameter write selection
to
change the setting of the restriction.
l
Refer to FR-E800 Function Manual for instruction codes for communication and availability of parameter copy, Parameter clear, and all
clear.
Simple
Simple
Simple
Parameter 0 to 99
Para-
meter
Name
Setting Range
Initial
Value
*1
0
Torque boost
0% to 30%
6/5/4/3/
2%
*2
1
Maximum
frequency
0 to 120 Hz
120 Hz
2
Minimum
frequency
0 to 120 Hz
0 Hz
3
Base
frequency
0 to 590 Hz
Gr.1: 60 Hz
Gr.2: 50 Hz
4
Multi-speed setting
(high speed)
0 to 590 Hz
Gr.1: 60 Hz
Gr.2: 50 Hz
5
Multi-speed setting
(middle
speed)
0 to 590 Hz
30 Hz
6
Multi-speed setting
(low speed)
0 to 590 Hz
10 Hz
7
*3
Acceleration
time
0 to 3600 s
5 s
*2
10 s
*2
15 s
*2
8
*3
Deceleration
time
0 to 3600 s
5 s
*2
10 s
*2
15 s
*2
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
9
Electronic thermal O/
L relay
Rated motor
current
0 to 500 A
Inverter
rated
current
10
DC injection brake
operation frequency
0 to 120 Hz
3 Hz
11
DC injection brake
operation time
0 to 10 s, 8888
0.5 s
12
DC injection brake
operation voltage
0% to 30%
6/4/2/1%
*2
13
Starting frequency
0 to 60 Hz
0.5 Hz
14
Load pattern
selection
0 to 3
0
15
Jog frequency
0 to 590 Hz
5 Hz
16
*3
Jog acceleration/
deceleration time
0 to 3600 s
0.5 s
17
MRS/X10 terminal
input selection
0 to 5
0
18
High speed
maximum frequency
0 to 590 Hz
120 Hz
19
Base frequency
voltage
0 to 1000 V,
8888, 9999
Gr.1: 9999
Gr.2: 8888
20
Acceleration/
deceleration
reference frequency
1 to 590 Hz
Gr.1: 60 Hz
Gr.2: 50 Hz
Para-
meter
Name
Setting Range
Initial
Value
*1
Simple
Simple
Simple
Simple
Simple
Simple
Summary of Contents for 800 Series
Page 10: ...4 INSTALLATION AND INSTRUCTIONS ...
Page 46: ...40 BASIC OPERATION ...
Page 64: ...58 INVERTER FAULT AND ALARM INDICATIONS ...
Page 70: ...64 SPECIFICATIONS ...