The rules of system configuration are explained below referring to a sample system configuration using an expansion board,
expansion adapter, I/O module, and intelligent function module.
System configuration example
The following system configuration is under consideration.
Check of limitation on the number of modules
Check if the sample system configuration is within the connectable-module range.
■
Number of connected expansion boards
(
Page 52 Number of connected expansion boards)
■
Number of connected expansion adapters
(
Page 52 Number of connected expansion adapters)
■
Number of connected extension modules
• Number of modules connected on whole system
(
Page 53 Overall system limitation)
• Number of modules connected to the CPU module
(
Page 53 Connection to the CPU module)
Type
No. of modules used Limitations
Judgment
Expansion board
1
Only 1
OK
Type
No. of modules used Limitations
Judgment
Expansion adapter (Communication)
2
Up to 2
OK
Type
No. of modules used Limitations
Judgment
Extension module
11
Up to 16
(Extension power supply modules and connector
conversion module are excluded.)
OK
Bus conversion module
1
Only 1
OK
Type
No. of modules used Limitations
Judgment
Total No. of I/O modules, intelligent function modules, and bus conversion modules
11
Up to 12
OK
Total No. of intelligent function module and bus conversion modules
7
Up to 8
OK
FX5U-32MR/ES
FX5-16EYR/ES
FX5-16EYT/ES
FX5-16EX/ES
FX5-232ADP
FX5-232-BD
FX5-485ADP
FX5-CNV
-BUS
FX5-40SSC-S
FX3U-1PG
FX3U-4AD
FX3U-128ASL-M
FX3U-4LC
FX3U-64CCL
CC-Link
FX5-16EYT/ES
To CC-Link
master station
The number of transmission points
setting for AnyWireASLINK
64 points
Remote I/O
station
Remote I/O
station
Remote I/O
station