3.3 Power Supply Specifications
The following describes the power supply specifications for the GT15.
3.3.1 For GOTs powered from the 100 to 240VAC power supply
3.3.2 For GOTs powered from the 24VDC power supply
Remark
Operation at momentary failure
• If an instantaneous power failure occurs in the power supply and continues
for more than the permissible period, the GOT will be reset.
• Make sure to power on the unit more than 5 seconds after power-off.
3.3.1
For GOTs powered from the 100 to 240VAC power supply
Item
Specifications
GT1595-XTBA
GT1585V-STBA,
GT1585-STBA
GT1575V-STBA, GT1575-
STBA, GT1575-VTBA,
GT1575-VNBA, GT1572-
VNBA, GT1565-VTBA,
GT1562-VNBA
Input power supply voltage
100 to 240VAC (+10% -15%)
Input frequency
50/60Hz 5%
Input max. apparent power
110VA (maximum load)
Power consumption
56W or less
41W or less
39W or less
At backlight off
30W or less
28W or less
Inrush current
50A or less (4ms)
(maximum load)
45A or less (4ms)
(maximum load)
40A or less (4ms)
(maximum load)
Permissible instantaneous
power failure time
20ms or less (100VAC or more)
Noise immunity
1,500Vp-p noise voltage, 1µs noise width (when measuring with a noise simulator
under 25 to 60Hz noise frequency)
Dielectric withstand voltage
1500VAC for 1 minute across power terminals and earth
Insulation resistance
10M or more across power terminals and earth by a 500V DC insulation resistance
tester
Applicable wire size
0.75 to 2 [mm
2
]
Applicable solderless terminal
Solderless terminal for M3 screw RAV1.25-3, V2-S3.3, V2-N3A,
FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
0.5 to 0.8 [N•m]