Operation | 22
Query Alarm Status
Command
Parameters
Query Command Sequence:
Q
Unit Response:
Qabe (for 1:1 Systems)
Qabce (for 1:2 Systems)
Qabcde (for Dual 1:1 Systems)
a = A1, Amplifier 1 (0 = Normal, 1 = Fault)
b = A2, Amplifier 2 (0 = Normal, 1 = Fault)
c = A3, Amplifier 3 (0 = Normal, 1 = Fault)
d = A4, Amplifier 4 (0 = Normal, 1 = Fault)
e = Any Switch Alarm or Any Power Supply Alarm (0 = Normal, 1
= Fault)
ATTENUATION = ATT
The SET command requires two parameters. The first parameter is a single ASCII digit representing the attenuator/path
number. The second parameter is three ASCII digits in length representing the attenuation in tenths of a dB.
Command
Parameters
Remote Command Sequence: $ATTnTttt
Unit Response:
$ATT
The QUERY command requires one parameter. The parameter is a single ASCII digit representing the attenuator/path
number.
Command
Parameters
Remote Command Sequence: ?ATTn
Unit Response:
?ATTnTttt
n = attenuator/path number
T = attenuation indicator
ttt = attenuation in tenths of a dB
For a 1:1 system with Input Attenuator
n = 1 = Input Attenuator
For a 1:1 system with Output Attenuator
n = 1 = Output Attenuator
For a 1:1 system with Input and Output Attenuators with no Slope
n = 1 = Input Attenuator
n = 2 = Output Attenuator
For a 1:1 system with Input and Output Attenuators with Slope
n = 1 = Module 1 in Primary Path
n = 2 = Module 1 in Standby Path
n = 3 = Module 2 in Primary Path
n = 4 = Module 2 in Standby Path
For a 1:2 or a Dual 1:1 system with Input Attenuators
n = 1 = Input Attenuator for Primary Path 1
n = 2 = Input Attenuator for Primary Path 2
For a 1:2 or a Dual 1:1 system with Output Attenuators
n = 1 = Output Attenuator for Primary Path 1
n = 2 = Output Attenuator for Primary Path 2
For a 1:2 or a Dual 1:1 system with Input and Output Attenuators with no Slope
n = 1 = Input Attenuator for Primary Path 1
n = 2 = Input Attenuator for Primary Path 2