Missouri Wind and Solar 3PAL-DIG-12V Information And Custom Programming Instructions Download Page 1

C

opyright © Missouri Wind and Solar, LLC 2014

 

Remove and safely brake charging sources 
such as wind/solar/hydro. When in doubt, use a 
qualified electrician. Missouri Wind and Solar, 
LLC is not responsible for damages or injuries 
caused by misuse or improper programming. 

DANGER! SHOCK WARNING: Wind, solar, 
hydro, batteries etc. may produce lethal 
voltages! Use extreme caution. 
 
Preset controller configuration 

(use ½ these 

voltages for a 12v system)

divert relay on at 

28.8 battery volts, start relay off timer at 27.2 
battery volts, relay off timer 5 seconds after 
27.2 volts is reached. If battery voltage does 
not fall below 27.2 volts, the relay will stay on.  
 
WE RECOMMEND YOU DO NOT CHANGE 
THE CONTROLLER

’S SETTINGS UNLESS 

YOU ABSOLUTELY NEED TO. READ AND 
UNDERSTAND ALL INSTRUCTIONS 
INCLUDED WITH YOUR EQUIPMENT. 
WARRANTY WILL BE VOID IF THE 
SETTINGS ARE CHANGED 
UNECCESSARILY.  

 
Possible reasons to change settings

:  

You have an inverter charger or other charge 
controller which may charge batteries to above 
28.8 volts. If another charging source performs 
an equalize charge, you can leave the factory 
settings alone and safely disconnect the 
Missouri Wind Digital Controller while an 
equalize charge is taking place.  

Outback Inverter Charger/Grid feed 
inverters

: Typically adjust the DIG controller 

high volt trip point to 15 volts (12v system) or 
29.5 volts (24v system). 

To change settings:  

1.  Connect the small sense wires to proper 

battery voltage or use a dc power supply 
(red wire +, black wire -).  

2.  Wait 6 seconds.  
3.  Use the two black push buttons below volt 

meter 

“set” & “enter.”  

You will be entering P-1 for time setting, P-3 
for voltage set points.  

4.  Hold 

“enter” until you see “P-3 display”, 

then release.  

5.  Short press 

”set” until you see “P-1” 

display. This is the time setting. Time 
setting is recommended for experienced 
users as this changes the amount of time 
the relay is on after battery falls to 27.2v, or 
13.6v.  

6.  Press 

“enter.” You will see “005.” This is 5 

seconds. Short press 

“set” to move the 

flashing digit from left to right. Stop on the 
digit for the preferred setting. Press 

“enter” 

to confirm the new setting.  

If you pass the desired digit, continue to 
short press 

“set” until you cycle back 

around to it.  

7.  After first 3 digits are changed, press 

“set” 

to view the second set of 3 digits. This is 
the relay activity timer (RAT). Relay activity 
timer starts countdown every time the relay 
turns off. The RAT time period is preset at 
5 seconds.  

Relay Activity Timer:

 Assuming the RAT is 

005 (5 seconds), when the relay has activity 
(turns on then off) the RAT will immediately 
start a countdown from 5 to 0 seconds.  
 
If the relay turns on again before the 
countdown reaches 0, the relay will stay on for 
10 seconds then relay off and RAT countdown 
starts from 5 to 0 seconds again.  
 
If the relay turns on again before countdown 
reaches 0, the relay will stay on for 20 seconds 
then relay off and RAT countdown starts from 5 
to 0 seconds again.  

If the relay does not turn on again before RAT 
countdown reaches 0, then the next time the 
relay turns on again it will be on for 5 seconds.  
 
The relay must turn on again before the RAT 
time reaches 0, otherwise the relay

’s on time 

will stay at 5 seconds.  
 
The RAT's purpose is to hold the controller in 
divert for an increasing amount of time 
because your controller is repeatedly diverting 
within a short period of time (i.e. batteries 
nearing full). 
 
Referring to the example above, 20 seconds is 
the maximum amount of time the relay will stay 
on if the conditions continue to be met. If you 
change the RAT (the second set of 3 digits) to 
20 seconds (020 on display), then relay on time 
will be 20 sec, 40 sec, 80 sec, 80 sec, 80 sec., 
etc. 

In most systems there is no need to 

change the RAT.

 

8.  The third set of digits will appear as: d-9. 

This means the LED display will turn off 
after 9 minutes if no buttons are pressed 
(user is not changing settings). Changing to 
d-0 means the display will always remain 
on.  
You can turn the display back on at any 
time by short pressing any button.  

9.  After the third set of digits, you will see your 

first time setting with no flashing digits. 
Hold 

“enter” until you see P-1.  

You are now done with the time (P-1) 
settings.  

Stop, do not press any buttons or make 
changes.

  

10. If you don't need to change the preset high 

or low voltage points, you still need to enter 
into P-3 directly after programming P-1. If 
this is the case, short press 

“set” until you 

Missouri Wind and Solar Digital Charge Controller Information and Custom Programming Instructions (WHITE COVER MODELS) 

Whether or not you will be changing the settings, read and understand these instructions thoroughly. Failure to do so can cause damage to the 
controller or system components

.

 

Reviews: