background image

7

3.0   

Functional Setup

3.1  Jumpers

3.2  Potentiometer

VR1 is a potentiometer used for LCD contrast adjustment and is located in the top left corner
of the RAM-300LCD board.

Table 1  Jumpers

Jumper

Jumper Function

JW1

FACTORY USE ONLY (JUMPER OFF)

JW2

FACTORY USE ONLY (JUMPER INSTALLED)

JW3

FACTORY USE ONLY (JUMPER INSTALLED)

JW8

CUT jumper to set the RAM-300LCD as an ancillary device.  Use NP-2051 blank labels 
to cover the System Reset, Signal Silence, Fire Drill, Enter, Menu and Cancel buttons 
for the Ancillary Device Feature.  Only Buzzer Silence, Lamp Test and Info are used.

SYSTEM

RESET

SIGNAL

SILENCE

FIRE

DRILL

BUZZER

SILENCE

LAMP

TEST

1

4

7

*

2

5

8

0

3

6

9

#

ENTER

MENU

CANCEL

INFO

ABC

DEF

GHI

JKL

MNO

PRS

TUV

WXY

QZ

A.C. ON

ALARM

SUPV

TRBL

CPU FAIL

   SYSTEM NORMAL

18:01 MON 2011-02-07

24V IN/OUT

1 2 3 4 5 6 7 8

ON

1 2 3 4

ON

VR1

JW1

JW2
JW3

P2

P1

SW30

SW31

+

-

S

RS-485 IN/OUT

SW31 DIP Switch
for various
system functions

JW1, JW2, JW3 ARE

FOR FACTORY USE

LEAVE JUMPERS

JW2 AND JW3 IN

PLACE.

LCD CONTRAST
ADJUSTMENT

THESE PINS ARE

FOR FACTORY USE

ONLY

THIS
CONNECTOR IS
FOR FACTORY
USE ONLY

CUT JUMPER JW8 TO
MAKE RAM-300LCD AN
ANCILLARY DEVICE.

JW8

-    +

SW30 DIP Switch for annunciator
address setting.  Valid addresses
1 to 7.

Place the 120 ohm
EOL resistor between 
+ and - terminals of 
the RS-485 on the 
last annunciator 
only.

Figure 3    Annunciator Component Descriptions

firealarmresources.com

Summary of Contents for RAM-300LCD Series

Page 1: ...AM 300LCD Series FA 300 SERIES Remote Annunciator SYSTEM RESET SIGNAL SILENCE FIRE DRILL BUZZER SILENCE LAMP TEST 4 1 7 2 5 8 0 3 6 9 ENTER MENU CANCEL INFO ABC DEF GHI JKL MNO PRS TUV WXY QZ A C ON A...

Page 2: ...firealarmresources com...

Page 3: ...otentiometer 7 3 3 DIP Switches 8 4 0 Wiring 9 5 0 Specifications Features 11 5 1 Enclosure 11 5 2 Electrical Specifications 11 5 3 Current Drain for Battery Calculations 11 5 4 Environmental Specific...

Page 4: ...2 Mechanical Installation 6 Figure 3 Annunciator Component Descriptions 7 Table 1 Jumpers 7 Table 2 RAM 300LCD Address DIP Switch Setup 8 Table 3 DIP switch SW31 settings 8 Table 4 Maximum Wiring Run...

Page 5: ...ional Setup section following This annunciator may be selected to operate as an ancillary device using DIP Switch SW31 6 to disable all buttons except Lamp Test Buzzer Silence Info and Arrow Buttons N...

Page 6: ...This enclosure may also be mounted to a 4 square electrical box There are two conduit areas provided at the bottom center of the enclosure With the dead front plate removed you may do the functional s...

Page 7: ...AL SILENCE FIRE DRILL BUZZER SILENCE LAMP TEST 1 4 7 2 5 8 0 3 6 9 ENTER MENU CANCEL INFO ABC DEF GHI JKL MNO PRS TUV WXY QZ A C ON ALARM SUPV TRBL CPU FAIL SYSTEM NORMAL 18 01 MON 2011 02 07 24V IN O...

Page 8: ...ON ON ON Note SW30 4 DIP switch is not used Note For the FX 350 351 Series Fire Alarm Panels if the number of annunciators programmed is 5 then the first five addresses 1 to 5 inclusive must be assign...

Page 9: ...ain for Battery Calculations on page 11 and calculate the Maximum current for all annunciators summed together Note All circuits are power limited and must use type FPL FPLR or FPLP Power Limited Cabl...

Page 10: ...m E O L resistor connected to the RS 485 positive and negative terminals 24V IN OUT S RS 485 IN OUT S R S 4 8 5 24V IN OUT S RS 485 IN OUT RAM 300LCD ADDRESS 1 RAM 300LCD ADDRESS 2 FA 300 FIRE ALARM P...

Page 11: ...5 3 Current Drain for Battery Calculations The maximum normal current drain will be during Lamp Test when all lamps are illuminated on one chassis at a time Thus the currents are Normal Standby 56 mA...

Page 12: ...ain for normal system operation Note Auxiliary relays will not operate when Fire Drill is operated Lamp Test Press the Lamp Test button momentarily to test all indicators except the CPU Fail LED All i...

Page 13: ...em a substitute for property owners renters or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation Building automation systems produced by the Mircom...

Page 14: ...ovide timely warning of fires caused by carelessness or safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits or...

Page 15: ...ication appliances such as sirens bells horns or strobes may not warn or waken a sleeping occupant if there is an intervening wall or door It is less likely that the occupants will be alerted or awake...

Page 16: ...5 Tel 905 660 4655 888 660 4655 Fax 905 660 4113 Mircom 2018 Printed in Canada Subject to changewithout priornotice www mircom com CANADA Main Office 25 Interchange Way Vaughan ON L4K 5W3 Tel 905 660...

Reviews: