INSTALLATION INSTRUCTIONS

RAM-2200-8 Eight-Zone LED Expander for FX-2200 
Fire Alarm Control Panel

The RAM-2200-8 provides up to 24 Zone LEDs (8 alarm LEDs, 8 supervisory LEDs, 
and 8 trouble LEDs per module) for the FX-2200.

Parts List

Qty 1 ... RAM-2200-8 module

Qty 4 ... #4 Hex Nuts

Qty 4 ... #4 Lock Washers

Qty 1 ... Ribbon Cable

Qty 1 ... Zone Label

NOTE: This component must be included in the control panel battery 
calculation. Refer to the Battery Calculation Sheet in the FX-2200 Installation 
Manual (LT-2000MIR) included with the control panel.

Installing the RAM-2200-8 Module

Before mounting the RAM-2200-8, fill out the Zone Label and insert it behind the 
overlay.

1.

Remove the right most black plate as viewed with dead front open.

2.

Mount the RAM-2200-8 assembly to the dead front using the 4 nuts/lock washers.

3.

If this is the first LED Expander: Connect the enclosed ribbon cable from “Output” 
on the display board to “CON1 IN” on the RAM-2200-8 module. 

If there is already at least one LED Expander present: connect one end of the 
enclosed ribbon cable to “CON2 OUT” on the LED Expander to the right of the 
new one. Connect the other end of the ribbon cable to the newly installed RAM-
2200-8 at “CON2 IN”.

In no event shall Mircom be liable for any direct, indirect or consequential damages, 
loss of anticipated profits, loss of time or any other losses incurred by the buyer in 
connection with the purchase, installation or operation or failure of this product.

Important!

Mircom recommends that the entire system be completely tested on a regular basis. 
However, despite frequent testing and due to but not limited to, criminal tampering or 
electrical disruption, it is possible for this product to fail to perform as expected.