WIRING GUIDE

All wiring must be installed in compliance with the Canadian Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the 
event of a fire.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) as shown in the wiring 

diagram. (See Figure 2.)

2.   Set the desired address on the sensor address switches. (See Figure 1.) 
3.   Install the sensor into the sensor base. Push the sensor into the base while 

turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control panel and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

FIGURE 2. WIRING DIAGRAM

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

ULC Listed Compatib

le

Control P

anel

CAUTION: Do not loop wire under 

terminal 1 or 2.  Break wire run to 

supervise connections.

CLASS A OPTIONAL WIRING

Remote 

Annunciator

(–)
(+)

RA

+

+

RA

+

+

RA

+

+

 

C0129-11

TAMPER-RESISTANCE

Intelligent photoelectric smoke sensors include a tamper-resistant capability 
that prevents removal from the base without the use of a tool. Refer to the 
base manual for details on making use of this capability.

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Operating Current @ 24 VDC:  

200 uA (one communication every 5 seconds with green LED blink on communication)

Maximum Alarm Current:  

2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)

Maximum Current:  

4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range: 

32°F to 122°F (0°C to 50°C)

Air Velocity: 

0 to 4000 ft./min. (0 to 1219.2 m/min.) 

Height: 

2.0˝ (51 mm) installed in B300A-6 Base

Diameter: 

6.2˝ (156 mm) installed in B300A-6 Base; 4.1˝ (104 mm) installed in B501 Base

Weight: 

3.4 oz. (95 g)  

Isolator Load Rating:  

0.0063*

*Please refer to your isolator base/module manual for isolator calculation instructions.

CAN/ULC S529 listed for Open Air Protection. 
This sensor must be installed in compliance with the control panel system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 
installed in compliance with CAN/ULC S524. 

GENERAL DESCRIPTION

MIX-2351APA  is a plug-in type smoke sensor that combines a photoelectronic 
sensing chamber with addressable-analog communications.
The sensors transmit an analog representation of smoke density over a com-
munication line to a control panel. Rotary dial switches are provided for set-
ting the sensor’s address. (See Figure 1.) 

FIGURE 1. ROTARY ADDRESS SWITCHES

 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

 C0162-00

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator  
(P/N RA100ZA). 
Mircom panels offer different features sets across different models. As a result, 
certain features of the photoelectric sensors may be available on some control 
panels, but not on others. MIX-2351APA supports Advanced Protocol and CLIP 
(Classic Loop Interface Protocol) mode.  
The possible features available if supported by the control panel are:
1.   The sensor’s LEDs can operate in three ways—on, off, and blinking–and 

they can be set to red, green, or amber. This is controlled by the panel.  

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

3.   Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the ULC listed control panel for spe-
cific operation. The photoelectric sensors require compatible addressable 
communications to function properly. Connect these sensors to listed-compat-
ible control panels only. 

SPACING

Mircom recommends spacing sensors in compliance with CAN/ULC S524. In 
low air flow applications with smooth ceilings, space sensors 30 feet apart 
(9.1 m). For specific information regarding sensor spacing, placement, and 
special applications, refer to CAN/ULC S524 or the System Smoke Detector 
Application Guide, available from Mircom. 

NOTE:

 Intelligent photoelectric smoke sensors are also listed for use inside 

DNRA duct smoke detectors. 

Duct Applications: 

MIX-2351APA is listed for use in ducts. See Duct Smoke 

Detectors Applications Guide HVAG53 for details on pendant mount applications. 

NOTE:

 Intelligent photoelectric smoke sensors are also listed for use inside 

DNRA duct smoke detectors.

I56-6722-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

MIX-2351APA  

Advanced Protocol 

Intelligent Photoelectric Smoke Sensors

Mircom Technologies Ltd.

25 Interchange Way, Vaughan ON, L4K 5W3

Tel: 905-660-4655, FAX: 905-660-4113

  

I56-6722-000 

 

 10/22/2020