73
Pre-Programmed Modes
12.3
Mode 3: Agent Release, Dual Hazard, Cross-zoned, Split
Release
12.3.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area 1, Cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area 1, Cross-zoned)
•
Detection Zone -3: Alarm (Hazard Area 2, Cross-zoned)
•
Detection Zone -4: Alarm (Hazard Area 2, Cross-zoned)
•
Detection Zone -5: Abort/Manual Release Combination (Hazard Area 1)
•
Detection Zone -6: Abort/Manual Release Combination (Hazard Area 2)
•
NAC -1: Escalating Signal, indicates Hazard Area 1 state
•
NAC -2: Escalating Signal, indicates Hazard Area 2 state
•
RAC -1: Releasing Circuit (Hazard Area 1)
•
RAC -2: Releasing Circuit (Hazard Area 2)
12.3.2 Hazard Configuration
•
Default Release Timer Value: 60 seconds
•
Default Manual Release Delay: 0 seconds.
•
Default Abort Delay Type: Standard UL.
•
Default Soak Timer Value: 0 seconds
12.3.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
•
Hazard Idle: Off
•
Hazard Alert: Temporal (see Table 7)
Detection Zones
Phantom Zones
Release Timers
Z1
Z2
Z3
Z4
Z5
Z6
Zp1
Zp2
RT1
Exp
RT2
Exp
Alm
Alm
Alm
Alm
AB/MR
AB/MR
Z1+Z2
Z3+Z4
Out1
Signal
Steady
X
X
Out2
Signal
Escalating
X
X
Out3
Rel.
Releasing
X
X
Out4
Rel.
Releasing
X
X
RLS TMR 1 Started
X
RLS Tmr 1 Interrupted
X
RLS Tmr 1 Cancelled
X
RLS Tmr 2 Started
X
RLS Tmr 2 Interrupted
X
RLS Tmr 2 Cancelled
X
Note:
Dual hazard operation is not permissible for UL/ULC operation.
i
Summary of Contents for FR-320 Series
Page 2: ......