56
Configuration
10.6
2. Set Time (Command-Menu)
Command Menu-->Panel Config-->Features
16. Sig-Sil NAC
[X] NAC-1->Default
[X] NAC-2->Default
Use this function to set which NAC
circuits are silenceable or non-
silenceable.
Command Menu/FR-320 Config/Features/
17. Active EOL
[X] DISABLE->Default
[ ] ENABLE
Enable this function if using an
Active EOL. If ICAC-306 is used,
this function should be enabled
since the Class A Converter has
built in Active EOL resistors.
10.5.3 Command Menu-->Panel Config-->Default Config
Command Menu-->Panel Config-->
Default Config
4. Default Config
Y-->Default
Use this function to reset the panel
to the default configuration of the
chosen programming mode.
Note:
10.3 How to Use the Keypad to Program the FR-320 on page 49
for
detailed instructions on making menu selections.
Command Menu/Set time Date
1. Daylight saving time
[X] DISABLE ->Default
[ ] ENABLE
Use this function to enable daylight savings
time.
Command Menu/Time Clock
2. Set time and date
Default
00:00 MON 2000-01-01
Use this function to set the time and date.
Use the “LEFT” and “RIGHT” keys to move
the cursor to the desired location in the
display and use the “UP” and “DOWN” keys
to increase or decrease the values. Press
the “ENTER” key to accept the changes and
the “CANCEL” key to ignore the changes.
Note:
time is in 24hr format
S i l en c eabl e N AC
[X ] N AC-1
Ac ti ve EOL
[X ] D I S AB LE
Lo ad th e defau l t
S etti n gs? Y
i
1. Daylight Save
2. Time Clock
3. Compensation
D a y l i g h t S a v i n g
[ X ] D I S A B L E
HH:MM WKD YYYY-MM-DD
00:00 MON 2000-01-01