52
Configuration
10.5.2 Command Menu-->Panel Config-->Hazard Config
Note:
10.3 How to Use the Keypad to Program the FR-320 on page 49
for
detailed instructions on making menu selections.
Command Menu-->Panel Config-->
Hazard Config
1. Release Timer
60->Default
Available options:
0,5,10,15,20,25,30,35,40,
45,50,55,60 seconds
Use this function to set the
programmable timer that delays the
activation of the releasing application
circuits.
This timer starts immediately after
receiving a confirming alarm (cross-
zoned hazard area) or a single alarm
(non-cross-zoned hazard area).
When the timer expires, the releasing
circuit activates.
Value: 0 to 60 seconds in five-second
increments.
Command Menu-->Panel Config-->
Hazard Config
2. Abort Delay
[X] Standard UL->Default
[ ] IRI
[ ] NYC
[ ] Local Juris.
Use this function to set how the Abort
Switch operates with the Release
Timer.
Note that if the Release Timer is set
to zero, the Abort Switch does not
operate.
In
Standard UL
mode, the release
timer will stop and hold when the
Abort Switch is pressed. When the
switch is released, the Release Timer
restarts from whichever is greater: the
remaining time on the timer or 10
seconds.
In
IRI
mode, the switch works in the
same way as it does in Standard UL
mode, except that the switch will
function only if it is pressed and held
before the second alarm comes in.
In
NYC
mode, pressing the Abort
Switch will reset to the Release Timer
and add 90 seconds to the configured
timer duration. After the Abort Switch
is released, the Release Timer will
restart.
In
Local Juris.
(Local Jurisdiction
Delay), pressing the Abort Switch will
reset the Release Timer back to its
configured value. After the switch is
released, the Release Timer will
restart.
-Haz ar d P ar am . -
1. R el ease ti m er
2. Abo r t D el ay
3. M an u al R l s
D el ay
4. S o ak ti m er
i
R e le a s e t im e r(s e c):
60
Abo r t D el ay Typ e:
[X ] S tan dar d UL