BPS-1100 Installation and Operation Manual
25
Table 3: Configuration Dip Switch Function Table
10.2 Entering Configuration Mode
The System enters Configuration Mode whenever any of the Configuration DIP Switches 2 to 8 are set to a “1" or
ON position (top position). The TEST / CONFIG MODE and COMMON TROUBLE LEDs will turn ON.
If there is no activity (no buttons pressed or switches changed) for one hour, the System will return to normal
operation, but will remain in trouble.
As Configuration DIP Switches are changed to select different functions, wait for a few seconds for the appropriate
LEDs to change as the System recognizes the change.
10.3 Exiting Configuration Mode
To exit Configuration Mode, after all desired changes are made, all Configuration DIP Switches must be returned to
a “0" or OFF position (bottom position). Wait about five seconds, then press the RESET button. The System should
now be back in Normal Operation.
Configuration Dip Switch Function Table
Dip Switch Position
(1-8)
Function
Number
Button
Operations
Description
0000 0000
00
None
Normal Operation (Not in Configuration Mode)
0000 0100
04
Select
Two Stage Operation
Features
0000 0110
06
Select
Output Circuit Correlations Enabled
0000 1101
0D
Select
Evacuation Code Selection
0001 0010
12
Select
Signal Circuit Isolator Option
0010 0000
20
Select
Alarm
Input
0010 0110
27
Select
General Alarm
0010 0100
24
Select
Non-latching Supervisory
0011 0000
30
Select
Signal
Indicating Circuits/
Signal Zones
0011 0010
32
Select
Strobe
0011 0011
33
Select
Non-silenceable Strobes
0011 1000
38
None
Show Relay Circuits
Relays
0100 0000
40
Select &
Confirm
Set Circuit Adder Module Number & Type
Resize System
0100 0001
41
Select
Correlation by Input Circuit
Correlations
0100 0010
42
Select
Correlation by Output Circuit
0111 1111
7F
Select &
Confirm
Restore to Default Configuration
Default
The BPS-1100 is not operating as a Signalling System while in Configuration Mode.
Note: