background image

12

English

Possible Cause

Symptom

What To Do

Press and release the On/Off/
Test button to start UPS

On/Off/Test button not
pushed

UPS will not turn on

Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce
the load on the UPS

UPS operates in
battery mode only,
even though there is
normal AC present

Input AC circuit breaker is
tripped

UPS has detected an
internal fault

 

 Call for service

Fault LED is
illuminated

The On-line/On-
Battery LED is
illuminated, but
there is no output

Incorrect service wiring

Disconnect the computer
cable from the UPS and press
the On button. If UPS works
normally, the software has
control of the UPS

The UPS is being
controlled via its
communications port

Site Wiring Fault
LED is illuminated

Have a Qualified Electrician
correct the service wiring

The batteries may be weak
or at the end of useful
service life

Charge the batteries for 8
hours and retest. If the runtime
is still less than expected, the
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated

UPS does not
provide expected
runtime

Weak/Bad Battery
LED is illuminated

Overload LED is
illuminated and a
constant alarm
The On-Line LED is
blinking and the au-
dible alarm is silent

UPS occasionally
emits a beep

Weak/bad batteries or  bad
connections at the battery

Normal operation

The load has exceeded the
UPS's capacity

The UPS is in either the
Boost mode or the Buck
mode

Check battery connections,
charge the batteries for 8
hours, replace the batteries

The UPS is performing its
intended function
Check the specifications (see
section 8). Remove part of the
load
The UPS is performing its
intended  function

Summary of Contents for PRO-E

Page 1: ...User s Manual PRO E SERIES...

Page 2: ...duction 2 2 Controls and Indicators 5 3 Installation 7 4 Operation 9 5 Troubleshooting 12 6 Replacing the Battery 13 7 Obtaining Service 16 8 Specifications 17 9 Configurable Parameters Settings 18 10...

Page 3: ...tion on customer support and factory service if it is required If you experience a problem with the UPS please refer to the Troubleshooting guide in this manual to correct the problem or collect enoug...

Page 4: ...s equipment has been tested and found to comply with the limits for a Class B computing device in accordance with the speci fications in Subpart J of Part 15 of FCC Rules and the Class B limits for ra...

Page 5: ...systems peritoneal dialysis systems neonatal ventilator incubators ventilators for both adults and infants anesthesia ventilators and infusion pumps as well as any other devices desig nated as critica...

Page 6: ...ower to the load The LED blinks and the audible alarm sounds when supplying battery power to the load The LED blinks and no audible alarm when the UPS is in either the boost or the buck mode The Fault...

Page 7: ...has a NEMA 5 15P Plug IEC 320 C14 socket for 230V models 7 The input circuit breaker will trip in the event the load exceeds the UPS s power rating 8 The RJ11 RJ45 modular connectors are used for 10 B...

Page 8: ...50 000 ft INSTALLATION Be sure to read the installation placement and all the cautions before installing the UPS Place the UPS in the final desired location and complete the rest of the installation p...

Page 9: ...can be used with the PRO E Series UPS Use only MINUTEMAN or MINUTEMAN approved interface cables with these UPSs Connect the interface cable Serial or USB to the appropriate communications port on the...

Page 10: ...start up or user invoked test This test will run for approximately fifteen seconds to measure the battery s capability to provide an acceptable amount of runtime If the UPS fails a self test one of t...

Page 11: ...ate and the alarm will beep three times every five min utes until the battery is reconnected or replaced If the battery is weak the Weak Bad Battery LED will illuminate and the alarm will beep one tim...

Page 12: ...esired cable connected The pinout for the port is depicted per the chart below Pin 1 EPO Emergency Power Off pull and hold this pin low to turn off the UPS release this pin from low to turn to restart...

Page 13: ...Site Wiring Fault LED is illuminated Have a Qualified Electrician correct the service wiring The batteries may be weak or at the end of useful service life Charge the batteries for 8 hours and retest...

Page 14: ...an still present a risk of electrical shock The current capability of a battery is sufficient to burn wire or tools very rapidly producing molten metal Observe these precautions when replacing the bat...

Page 15: ...AC power cord from the AC wall outlet 4 Unplug the equipment from the output receptacles of the UPS 5 Unplug the computer interface cable from the rear panel of the UPS 6 Remove the retaining screws...

Page 16: ...stall the battery bracket and the battery bracket retaining screw 17 Verify proper polarity Reconnect the battery negative black wire to the battery negative terminal 18 Verify proper polarity Reconne...

Page 17: ...s if possible F A technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue...

Page 18: ...Surge energy rating one time 10 1000 uS waveform Protection On battery waveshape Over current short circuit protected and latching shutdown Simulated Sine Wave On battery frequency 50 60 Hz 5 Hz unle...

Page 19: ...r environment or leave factory default Enter the current date when replacing batteries Use this function to uniquely identify the UPS in your network configuration Changes output voltage during batter...

Page 20: ...operly registered the product within 10 days of purchase The warranty shall be void if a the equipment is damaged by the customer is improperly used is subjected to an adverse operating environment or...

Page 21: ...s or otherwise The sole and exclusive remedy for breach of any warranty expressed or implied concerning Para Systems s prod ucts and the only obligation of Para Systems hereunder shall be the repair o...

Page 22: ...s 1455 LeMay Drive Carrollton Texas 75007 USA Type of Equipment Uninterruptible Power Supplies UPS Model No PRO500E Y PRO700E Y PRO1100E Y PRO1500E Y I the undersigned hereby declare that the equipmen...

Page 23: ...22 English Notes...

Page 24: ...Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000226 Rev 0...

Reviews: