  Turn on the UPS power switch ("1" position) and verify that the "AC Normal" LED

(Green) illuminates after a short delay.  This is the AC

 

Normal Mode.  Leave the UPS

in this position for approximately 30 seconds minimum.

  Depress the UPS "Test/Alarm Silencer"  rocker switch toward the "Test" position and

hold for 10 to 15 seconds.  Verify that the audible alarm sounds after a five (5)
second delay (twice every two (2) seconds), the "AC Fault" LED turns yellow and the
"AC Normal" LED extinguishes.  This is the Normal Inverter Mode (battery operation).

  Release the test switch and unit will return to the AC Normal Mode after a short

delay.

NOTE:  If any condition experienced during the above test procedure was not as
described, contact your supplier or Para Systems, Inc. customer service and report
any problem observed.  If tests proceeded normally, the UPS is ready for load
testing.

LOAD TESTING

  Turn off the UPS power switch and plug your critical load(s) into the UPS output

receptacle(s).  Then turn the power switch back on and turn on your loads.

  To verify that the UPS will accommodate the total load added:

1.  Ensure that data is saved prior to test in case power is lost during test.

2.  Depress the MINUTEMAN test switch for 10 to 15 seconds while running

maximum load power.  This testing should be repeated 5 to 10 times.

3.  Verify that UPS and load functions were proper during this testing (see items

under INSTALLATION AND PRELIMINARY TESTING for UPS function).  If
all functions were proper, the UPS is ready for operation.

OPERATION

After testing above, keep commercial power applied to the UPS with the power switch on for a
minimum of six (6) hours to permit full battery recharge.  Loads can be powered during recharge.
For daily operation you can turn on all UPS loads with the UPS power switch or you can leave the
UPS on and turn on your critical equipment each day.  With the standard UPS configuration, the
battery charger runs only when the power switch is on.  However, turning the unit off each night
and over the weekend will create no problems for the batteries or the charger.

When a brownout, power interruption, power outage, over-voltage condition or a drastic
frequency shift occurs or the AC fuse blows (AT650, AT800 or AT2300) or input breaker trips
(AT1200 or AT 1600), the MINUTEMAN UPS will switch to the normal inverter mode - "AC
Normal" LED will extinguish, audible alarm will sound after a five (5) second delay and the LED(s)
indicating the problem will illuminate.  A brownout will cause the "AC Fault" light to turn yellow, a
power interruption or outage will cause the "AC Fault" light to turn yellow and the "AC Fail" light to
illuminate (RED), an over-voltage condition will cause the "AC Fault" light

 

to turn red, a drastic

Summary of Contents for AT1200

Page 1: ...MODELS DESCRIBED IN THIS MANUAL AT650 GS650 650VA AT800 GS800 800VA AT1200 GS1200 1200VA AT1600 GS1600 1600VA AT2300 GS2300 2300VA OWNER S MANUAL...

Page 2: ...Physical Specifications 4 Unit Description 5 GS Models 6 Installation and Preliminary Testing 6 Load Testing 7 Operation 7 System Batteries 8 Battery System Checkout 9 UPS Monitoring Configurations 9...

Page 3: ...TRATION Locate your warranty registration card in the back of this manual and complete and return within 10 days of receipt of the unit s to register your warranty Failure to register your warranty re...

Page 4: ...igh short circuit current The current capability of each battery system is sufficient to burn large wire or tools very rapidly producing molten metal The following precautions should be observed when...

Page 5: ...00 800 560 50 220 4 0 220 3 6 48 8 20 382 AT1200 1200 840 60 120 11 1 120 10 0 48 7 18 573 GS1200 1200 840 50 220 6 1 220 5 5 48 7 18 573 AT1600 1600 1120 60 120 14 8 120 13 3 72 8 20 765 GS1600 1600...

Page 6: ...er Crest Factor Non Linear Load 3 1 Inverter Waveform Synchronized Computer Grade Sinewave Harmonic Distortion Less than 3 THD at full linear load Inverter Voltage Regulation Static 3 Dynamic 5 with 5...

Page 7: ...Audible Noise 40 dB ANSI Scale A at 3 UNIT DESCRIPTION AT SYCHRONIZED SINEWAVE MODELS 1 Power Switch 2 Alarm Silencer Test momentary rocker switch 3 AC Normal LED Green On when commercial voltage is...

Page 8: ...15P Plug standard or AWG 12 3 SJT AT2300 with NEMA L5 30P Plug 11 Input Fuse Holder Breaker At650 AT800 and AT2300 units use fuse and fuse holder at input AT1200 and AT1600 units use AC circuit break...

Page 9: ...r This testing should be repeated 5 to 10 times 3 Verify that UPS and load functions were proper during this testing see items under INSTALLATION AND PRELIMINARY TESTING for UPS function If all functi...

Page 10: ...y warning IF COMMERCIAL POWER RETURNS BEFORE THE WARNING SIGNAL THERE IS NO NEED TO SHUT DOWN YOUR SYSTEM AT ALL The MINUTEMAN will switch back to normal AC mode operation automatically During normal...

Page 11: ...ystems also offers its own software package Network Manage which functions with Novell Unix OS 2 LAN Manager LAN Server and MacIntosh Operating Systems Network Manager offers many advantages over exis...

Page 12: ...mon problems Do not remove the unit cover or attempt to service this unit There are no user serviceable components inside Unauthorized service will void the warranty COMMON UPS PROBLEMS No normal AC m...

Page 13: ...Other packaging methods can result in damage to the unit Enclose the name and telephone number of the person who can authorize repair charges inside the carton or packing list folder Also include you...

Page 14: ...INDIRECT INCIDENTAL CONSEQUENTIAL OR OTHER TYPES OR DAMAGES RESULTING FROM THE USE OF THIS PRODUCT OTHER THAN THE LIABILITY STATED ABOVE THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTIES EXPRESSED OR I...

Reviews: