Note:
As for the set value of [MIXING output time] and [MIXING inish output time], these are
common in [Batch inish] and [Discharge inish].
11.6.8
DISCHARGE mode
The DISCHARGE mode is a mode used when the object to be discharged after the
weighing is inished.
The Discharge signal is output from the connector pin set to [DISCHARGE] by the external
control I/O.
The output timing of the discharge signal (start discharge) can be set to each of
[OPERATION AT BATCH FINISH].
Refer to Chapter
[DISCH. MONI. TIMER] is the timer for occurring sequence error when it takes time for
discharge too much.
[DISCH. GATE CLOSE DELAY] is to set the time to close the gate after the measured value
meets the condition of ZERO BAND in discharge.
[DISCH. FINISH OUTPUT ON] is to set the output time of the discharge inish signal.
Refer to Chapter
In addition, [TARE CLEAR] and [MIXING START] is set as the morement after discharge
inish.
Refer to Chapter
11.6.9
Power on original point detection (POWER ON ORIGIN)
The power on original point detection detects the starting point sensor in the detection
time set when the power supply is turned on. The original point detection is completed
when the gate is at the position in which the original point sensor can be detected.
This setting is selectable from [EFFECTIVE] or [INVALID], and the range of detecting time
is 1 s to 15 s.
The default has set as [INVALID].
1. Select [MENU]
2. Select [SERVO CALIBRATION] in menu screen 1/2.
3. Select [POSITION CALIB.] in servo calibration screen.
4. Select [POWER ON ORIGIN] in position calibration screen.
5. Select [POWER ON ORIGIN] in position calibration screen after the power turns on,
and select from [EFFECTIVE] or [INVALID].
6. Tap [OK].
7. Select [DETECTION TIME], and input the detection time by ten keys.
8. Tap [OK].
Weight Controller CSD-918
11 Weighing mode
EN-118
Minebea Intec