TT115/TT155/TT165/TT297 Temptran
TM
2-wire Temperature Transmitter for RTD Thermometers
Installation and Operating Instructions
Page 1: ...Tel 763 571 3121 Fax 763 571 0927 www minco com TT115 TT155 TT165 TT297 TemptranTM 2 wire Temperature Transmitter for RTD Thermometers Installation and Operating Instructions...
Page 2: ...0 1 of Span Transmitter Linearity 0 1 of Span Physical Printed circuit board designed to mount inside the S470 series thermostat housing with RTD Operating Environment 32 to 122 F 0 to 50 C non conde...
Page 3: ...ran has been factory calibrated to its marked temperature range or to a specific RTD do not change its Zero or Span adjustments Wiring Diagram Figure 1 Power Supply DC power supply requirements are de...
Page 4: ...lliammeter still reads 4 0 mA 0 016 mA Correct if necessary then repeat steps 4 and 5 Transmitter Ranging The transmitter is initially calibrated to a specific temperature range as shown on the label...
Page 5: ...changed In the above example if the Zero trim pot cannot adjust the transmitter current down to 4mA with the 30 F Zero switch settings then the Zero switch settings should then be changed to 39 F OFF...
Page 6: ...33 36 ON OFF ON OFF 24 31 ON OFF OFF ON 15 26 ON OFF OFF OFF 6 21 OFF ON ON ON 3 16 OFF ON ON OFF 14 10 OFF ON OFF ON 23 5 OFF ON OFF OFF 32 0 OFF OFF ON ON 41 5 OFF OFF ON OFF 52 11 OFF OFF OFF ON 61...
Page 7: ...33 36 ON OFF ON OFF 24 31 ON OFF OFF ON 15 26 ON OFF OFF OFF 6 21 OFF ON ON ON 3 16 OFF ON ON OFF 14 10 OFF ON OFF ON 23 5 OFF ON OFF OFF 32 0 OFF OFF ON ON 41 5 OFF OFF ON OFF 52 11 OFF OFF OFF ON 6...
Page 8: ...inum 00375 1 4 20 mA DC Output H Temperature Range 4 mA Temp 20 mA Temp H 40 to90 F 4 to32 C Consult factory for current list of available ranges TT115PD1H Sample part number Warranty Items returned w...