Parameter Descriptions
P052
Tank Dimension ‘A’
This is dimension ‘A’ as used in the tank shape parameter (P050) on page 55.
Enter the height of the tank bottom if P050 = 2,3,4, or 5, or the length of one
end section of the tank if P050 = 7.
Enter the dimension in units (P005)
P053
Tank Dimension ‘L’
This is dimension ‘L’ as used in the tank shape parameter (P050) on page 55.
Enter the tank length (excluding both end sections) if P050 = 7.
Enter the dimension in units (P005)
P070
Fail-Safe Timer
The amount of time delay, in minutes, before going into fail-safe mode.
P071
Fail-Safe Material Level
Selects the default measurement in the event that the fail-safe timer expires.
Entry:
1 = high; maximum span value
2 = low; minimum span value
3 = hold; hold current value
P200
mA Range
Enables the mA output function by selecting the range and relationship to
span.
Entry:
1 = 0 to 20 mA
2 = 4 to 20 mA
3 = 20 to 0 mA
4 = 20 to 4 mA
P341
Run Time
View the accumulated number of days the IQ Radar 160/160 Ex has been
operating.
Summary of Contents for IQ Radar 160
Page 1: ...33455500 Rev 3 1 IQ RADAR 160 Instruction Manual PL 550 January 2001 Q RADAR I60 ...
Page 10: ...Page 10 IQ Radar 160 160 Ex PL 550 Specifications ...
Page 32: ...Page 32 IQ Radar 160 160 Ex PL 550 Installation ...
Page 35: ...PL 550 IQ Radar 160 160 Ex Page 35 Start Up Display Aiming the Hand Programmer ...
Page 40: ...Page 40 IQ Radar 160 160 Ex PL 550 Start Up ...
Page 52: ...Page 52 IQ Radar 160 160 Ex PL 550 Operation ...
Page 62: ...Page 62 IQ Radar 160 160 Ex PL 550 Parameter Descriptions ...
Page 66: ...Page 66 IQ Radar 160 160 Ex PL 550 Appendix I ...
Page 68: ...Page 68 IQ Radar 160 160 Ex PL 550 Appendix II ...
Page 74: ...Page 74 IQ Radar 160 160 Ex PL 550 Appendix III ...