Page 56
IQ Radar 160/160 Ex
PL-550
Parameter Descriptions
3 = parabolic bottom
4 = spherical bottom
5 = angled bottom
6 = flat ends
7 = parabolic ends
8 = sphere
Note:
Tank dimensions ‘A’ and ‘L’ are entered via parameters P052 and P053
respectively.
P051
Max Volume
For Readings in volumetric units (rather than percent), enter the vessel
volume between Empty (P006) and Span (P007).
The units of measurement for this reading are non-dimensional. The volume
is calculated from the empty position to the maximum position and is scaled
according to the Tank Shape (P050) value. This enables the use of any
volume units required.
Example
1.
If max. volume = 3650 m
3
, enter 3650.
2.
If max. volume = 267500 gallons, enter 267.5 (1000's of gallons).
Enter the volume of the tank at full (Factory = 1)