Page 50
IQ Radar 160/160 Ex
PL-550
Operation
Reset:
P999
master reset
Program:
P001
enter ‘1’
mode of measurement
= level
P002
enter ‘1’
material
= liquid
P003
enter ‘2’
measurement response
= 1m/min.
P004
enter ‘240’
antenna
= dielectric rod,
standard length
P005
enter ‘1’
units
= metres
P006
enter ‘5’
empty distance
= 9.6 m
P007
enter ‘4.5’
span
= 8.5 m
P652
enter tag value
offset correction
= factory
P800
enter tag value
blanking
= factory
P820
enter ‘1’
algorithm
= factory
P830
enter ‘4’
TVT type
= factory
Run:
Press run to start normal operation. Press
.
Application Example: Still Pipe
An alternate to the waveguide antenna, this option is also used for products
with an
ε
r
or less than 3 or if extremely turbulent or vortex conditions exist.
Note:
For
ε
r
< 3, the lower 40 cm of vessel level may not be measurable.
vent hole
100 mm (4”) diameter
Summary of Contents for IQ Radar 160
Page 1: ...33455500 Rev 3 1 IQ RADAR 160 Instruction Manual PL 550 January 2001 Q RADAR I60 ...
Page 10: ...Page 10 IQ Radar 160 160 Ex PL 550 Specifications ...
Page 32: ...Page 32 IQ Radar 160 160 Ex PL 550 Installation ...
Page 35: ...PL 550 IQ Radar 160 160 Ex Page 35 Start Up Display Aiming the Hand Programmer ...
Page 40: ...Page 40 IQ Radar 160 160 Ex PL 550 Start Up ...
Page 52: ...Page 52 IQ Radar 160 160 Ex PL 550 Operation ...
Page 62: ...Page 62 IQ Radar 160 160 Ex PL 550 Parameter Descriptions ...
Page 66: ...Page 66 IQ Radar 160 160 Ex PL 550 Appendix I ...
Page 68: ...Page 68 IQ Radar 160 160 Ex PL 550 Appendix II ...
Page 74: ...Page 74 IQ Radar 160 160 Ex PL 550 Appendix III ...