Page 90
AiRanger XPL Plus – INSTRUCTION MANUAL
7ML19981AN02
mmm
mm
Te
c
hnical Ref
e
re
nce
Parameter Settings For AO-10 mA Output # 00 (1 - 10)
Parameter Settings For Point # 7, 8, 9 and 10.
Ensure Point Number 00 is not still displayed or all programming will be cleared .
Parameter Settings For AO-10 mA Output # 7
With process control equipment disabled, enter the RUN mode to monitor system
performance. Otherwise, perform a Reading Measurement simulation (P920) to verify
programming.
When satisfied with system performance and programming:
• connect the AO-10 mA outputs 1 - 6 to the PLC as required.
• connect the AO-10 mA output 7 to the device indicating total material.
Note that on XPL Plus "power off" the AO-10 mA output is "held" and on AO-10 "power off"
the mA output drops to 0.00 mA. During a power interruption, the "last known" mA output
value is maintained in memory for 1 hour minimum. If power is interrupted beyond 1 hour,
on power resumption, the mA output immediately assumes the "new value".
P200
mA Range
No entry required (Empty = 4 ma; Full = 20 mA
when P001 = 1).
P219
mA Failsafe
Enter "3.8" for 3.8 mA output on "LOE".
P999
Master Reset
Press
with each unused Point
Number displayed.
P202
mA Allocation
Enter "1.6" for mA output # 7 equals the Point
Number 1 - 6 average.
Note:
If a Tripper Car is used to fill each section of the bunker, see Example 4 as well.
Summary of Contents for airanger XPL plus
Page 1: ...Instruction Manual March 2005 XPL PLUS airanger ...
Page 10: ...Page 6 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 26: ...Page 22 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 82: ...Page 78 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 106: ...Page 102 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 113: ......