Page 44
AiRanger XPL Plus – INSTRUCTION MANUAL
7ML19981AN02
mmmm
m
Enhancement P
a
ra
met
e
rs
Profile Records (P330 to P337)
The following parameters are for authorized Siemens Milltronics service personnel or
Instrumentation Technicians familiar with Siemens Milltronics echo processing
techniques.
Use these features to record and save a total of up to 10 Echo profiles, initiated manually
(P330), or automatically (P331 et al). See Scope displays (P810) for echo profile viewing
hardware / software requirements.
If 10 Echo Profiles are already saved, addresses 1 through 10 are filled, the oldest
automatically initiated record is overwritten. Manually initiated records are not
automatically overwritten. All records are automatically deleted in the event of a power
interruption.
When a record is displayed, results are based on current programming (which may have
been altered since the record was saved). This permits the effect on the echo profile to be
observed when changing an echo parameter.
P302 (V) TEMPERATURE, SENSOR MAX
Use this feature if vessel temperature is monitored by a TS-3 Temp Sensor to
view the highest temperature recorded (in °C).
When accessed, the TS-3 symbol is displayed in the Point Type field and the
TS-3 Number (corresponding to the XPL Plus terminals) is displayed in the Point
Number field.
values: -50 to 150
Summary of Contents for airanger XPL plus
Page 1: ...Instruction Manual March 2005 XPL PLUS airanger ...
Page 10: ...Page 6 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 26: ...Page 22 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 82: ...Page 78 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 106: ...Page 102 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 113: ......