mA Output Parameters (P200 to P203, P210 to P215,
P219)
If AO-10 mA outputs are to be used, alter the following parameters as required.
Otherwise, proceed to Operation.
When a mA Output Parameter is accessed, the mA symbol is displayed in the Point Type
field and the mA Output Number (corresponding to the AO-10 terminals) is displayed in
the Point Number field.
P200
mA RANGE
Enter the desired range of the mA output displayed.
value: 0 = OFF
20 mA = high level (unless P001 = 2 or 3, then 20
mA = low)
1 = 0 to 20 mA
2 = 4 to 20 mA
(preset)
3 = 20 to 0 mA
20 mA = low level (unless P001 = 2 or 3, then 20
mA = high)
4 = 20 to 4 mA
P201 mA
FUNCTION
Use this feature to alter the automatic mA output/measurement relationship, if
desired.
The mA Function automatically corresponds to "level", "space", or "distance"
based upon Operation (P001). If a Tank Shape (P050) is programmed, the mA
Function automatically corresponds to volume (unless the mA Allocation has
been altered).
values: 1 = level
2 = space
3 = distance
4 = volume