7ML19981AN02
AiRanger XPL Plus – INSTRUCTION MANUAL
Page 29
mm
mmm
Appl
icat
ion P
a
ra
met
e
rs
Reading Parameters (P060 to P062)
If Reading alteration is required, alter the following parameters to:
a. alter the number of decimal places displayed.
b. convert to units other than Units (P005), % of Span (P007), or Max Volume
(P051).
c. reference measurements to some point other than Empty (P006) or Span (P007).
If alteration is not required, proceed to Failsafe Parameters.
P060
DECIMAL POSITION
Enter the maximum number of decimal places to be displayed in the Reading.
In the RUN mode, the number of decimal places displayed is automatically
adjusted (if necessary) to prevent the number of Reading digits from exceeding
display capabilities.
This value is automatically altered when Max Volume (P051) is altered.
values: 0 = no digits after the decimal point
1 = 1 digit after the decimal point
2 = 2 digits after the decimal point
3 = 3 digits after the decimal point
P061
CONVERT READING
Enter the value to multiply the Reading by (before display).
This feature is preset to 1.000 (no conversion).
e.g.
If the Reading is currently displayed in feet, to display in yards, enter 3.
Avoid entering a value that, when multiplied by the maximum current reading,
could exceed 5 digits before the Decimal Position
values: -999 to 9999
Summary of Contents for airanger XPL plus
Page 1: ...Instruction Manual March 2005 XPL PLUS airanger ...
Page 10: ...Page 6 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 26: ...Page 22 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 82: ...Page 78 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 106: ...Page 102 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 113: ......