Application Parameters
Application Parameters are used to alter the XPL Plus display, failsafe, relay, and/or mA
output operation.
Volume Parameters (P050 to P055)
If Readings proportional to volume are desired, adjust the following parameters.
If Volume Conversion is not required, proceed to Reading Parameters.
P050
TANK SHAPE
Enter the Tank Shape option that matches the vessel monitored.
If the Tank Shape option selected requires additional vessel dimension entry, the
associated parameters (as indicated below) may be scroll accessed.
When Operation is "level" (P001 = 1), material volume is calculated. Alternatively,
when Operation is "space" (P001 = 2), remaining vessel capacity is calculated.
In the RUN mode, Readings are displayed in percent of (and mA outputs are
proportional to) maximum volume. To convert Readings to volumetric units, see
Max Volume (P051).
When monitoring solids, volume calculation accuracy may vary.
values: 0 = volume calculation not required (preset)
1 =
flat level bottom
or
A
4 =
half sphere bottom (P052)
8 =
sphere
A
or
2 =
cone / pyramid bottom (P052)
5 =
A
or
flat slope bottom (P052)
9 =
Universal Linear (P054 / P055)
3 =
A
parabola bottom (P052)
6 =
flat ends
7 =
A
L
parabola ends (P052 / P052)
10 =
Universal Curved (P054 / P055)
Summary of Contents for airanger XPL plus
Page 1: ...Instruction Manual March 2005 XPL PLUS airanger ...
Page 10: ...Page 6 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 26: ...Page 22 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 82: ...Page 78 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 106: ...Page 102 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 113: ......