Page 20
AiRanger XPL Plus – INSTRUCTION MANUAL
7ML19981AN02
mmm
mm
Quic
k St
ar
t P
a
ra
met
e
rs
P003
MEASUREMENT RESPONSE
Enter how quickly the XPL Plus is to respond to changing measurements.
Slower Measurement Response improves stability and reliability.
values: 1 = slow
2 = medium
3 = fast
4 = surge
5 = turbo
(0.1 m/min)
(1 m/min)
(10 m/min)
(1.7 m/sec)
(17 m/sec)
"Surge" and "turbo" are intended for equipment position monitoring. Use with
caution for level measurement. See Technical Reference Measurement
Response
P004
TRANSDUCER
Enter the type of transducer connected to the XPL Plus for the Point Number
displayed.
ULTRASONIC
ULTRASONIC / TEMPERATURE
values: 0 = not entered
1 = ST-25
2 = ST-50
3 = ST-100
4 = LR-21
5 = LR-13
100 = ST-H
101 = XCT-8
102 = XPS-10
103 = XCT-12
104 = XPS-15
105 = XPS-30
106 = XPS-40
107 = XLT-30
108 = XLT-60
109 = XLS-30
110 = XLS-60
111 = XKS-6
112 = XRS-5
P005 (G) UNITS
Enter the units of measure desired for programming Empty (P006) and Span
(P007).
values: 1 = meters (m)
2 = centimeters (cm)
3 = millimeters (mm)
4 = feet (ft)
5 = inches (in)
(preset)
Summary of Contents for airanger XPL plus
Page 1: ...Instruction Manual March 2005 XPL PLUS airanger ...
Page 10: ...Page 6 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 26: ...Page 22 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 82: ...Page 78 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 106: ...Page 102 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 113: ......