Interconnection
Before interconnecting system components to the XPL Plus terminals, verify all
components have been installed in accordance with the associated product instruction
manuals.
Connect all associated equipment cable shields to the XPL Plus shield connections. To
avoid differential ground potentials, do not connect cable shields to ground (earth)
elsewhere. Insulate (tape) cable shields at all shield junctions to prevent ground loops.
All field wiring must have insulation suitable for at least 250 V.
Hazardous voltage is present on transducer terminals during
operation.