Page 100
AiRanger XPL Plus – INSTRUCTION MANUAL
7ML19981AN02
mmm
mm
Tr
oub
leshoot
in
g Gui
d
e
If increasing Near Blanking is unacceptable (the transducer cannot be mounted higher)
see Auxiliary Transducer (P725). Otherwise, the TVT Curve must be raised in the area of
the false echo.
Connect an oscilloscope to the XPL Plus, (see
Enhancement Parameters
Scope Displays,
P810). Adjust the TVT Start Min (P833), TVT Start Duration (P834), and TVT Slope Min
(P835) slightly.
Continue making minor TVT Curve adjustments and taking new measurements while
observing the Echo Marker position until the Echo Lock Window repeatedly locks onto
the true echo. Verify the false echo is still ignored, regardless of the vessel material level,
or empty / fill activity.
Wrong Reading
If the Reading is erratic, or jumps to some incorrect value periodically, ensure the
following:
1. Material (object) surface monitored is not beyond the transducers maximum
range.
2. Material is not falling in the transducer sound beam.
3. Material ( P002 ) value matches the material monitored.
4. Measurement Response ( P003 ) is not set too fast.
5. Transducer ( P004 ) type entered matches the transducer used.
If the periodic incorrect value is always the same, see Fixed Reading. If the incorrect
value seems to be random, ensure the material surface to transducer distance is less
than the Empty value entered plus 20%. If the material / object monitored is outside this
distance, increase Range Extension (P801) as required.
If the material monitored is a liquid, check for splashing in the vessel. Increase
Measurement Response as required to stabilize the Reading, or install a stilling well
(contact Siemens Milltronics or your local distributor).
Access the Noise (P807) parameter. If the peak value jumps wildly, verify the transducer
cables are run in grounded metal conduit; separate from other wiring, and transducer
cable shields are connected to the XPL Plus shield terminals and not to ground
elsewhere.
If the XPL Plus is mounted in close proximity to (or transducer cables run near those of)
another ultrasonic level monitor, see Level System Sync (P726).
Temporarily disable nearby SCR control drives, high voltage or current contactors. If the
condition disappears, move the XPL Plus to another location.
Set Echo Lock (P711) to "max verification" (response to material level changes may be
slowed somewhat).
Increase the Confidence Threshold (small amounts at a time) while observing the results.
If performance is not improved return the Confidence Threshold to the preset value.
Connect an oscilloscope to the XPL Plus, (see
Enhancement Parameters
Scope Displays,
P810). While monitoring the Echo Marker, select the Algorithm (P820) best suited to the
material / conditions.
Summary of Contents for airanger XPL plus
Page 1: ...Instruction Manual March 2005 XPL PLUS airanger ...
Page 10: ...Page 6 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 26: ...Page 22 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 82: ...Page 78 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 106: ...Page 102 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Page 113: ......