
OM-244 243 Page 14
3-12. Filling Coolant Tank
.
Operating cooler when coolant
is low can damage cooler and
torch components. Always
have proper amount of coolant
in tank and use coolant recom-
mended by the manufacturer.
1
Coolant Tank Cap
2
Coolant Level Indicator
.
Remove shielding gas cylinder
from rear of unit to fill coolant
tank.
Unscrew cap from tank.
Use table to select proper coolant,
and fill tank until coolant appears in
upper half of indicator.
Check coolant level after attaching
torch coolant hoses and running
cooler. Be sure coolant appears in
upper half of indicator. Add coolant
if necessary.
Rear View
MILLER Low Conductivity
Coolant No. 043 810**;
Distilled Or Deionized Water
OK Above 32
°
F (0
°
C)
MILLER Low Conductivity
Coolant No. 043 810**; Or
MILLER Aluminum Protecting
Coolant No. 043 809**;
Distilled Or Deionized Water
OK Above 32
°
F (0
°
C)
GTAW Or Where
HF* Is Used
GMAW Or Where
HF* Is Not Used
Application
*HF: High Frequency Current
**MILLER coolants protect to -37
°
F (-38
°
C) and resist algae growth.
Coolant
MILLER Aluminum
Protecting Coolant
No. 043 809**
Where Coolant Contacts
Aluminum Parts
NOTICE
−
Use of any coolant other than those listed in the table voids the warranty on any parts
that come in contact with the coolant (pump, radiator, etc.).
1
2
Ref. 956142645-4-5
3-13. Electrical Service Guide
Elec Serv 2009
−
08
.
Actual input voltage should not exceed
±
10% of indicated required input voltage. If actual input voltage is outside of this range, output may not
be available.
50/60 Hz Three Phase
Input Voltage (V)
400
Input Amperes (A) At Rated Output
17
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
20
Normal Operating Fuses
3
25
Min Input Conductor Size In mm
2
,
4
2.5
Max Recommended Input Conductor Length In Meters
41
Min Grounding Conductor Size In mm
2
,
4
2.5
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5”. See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.