OM-363 Page 22
3-19. Electrical Service Guide
A. For 250 DX Models
All values in both tables were calculated at 60% duty cycle.
Actual input voltage cannot exceed
±
10% of indicated required input voltage shown in both tables. If actual input voltage is outside of this range,
damage to unit may occur.
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
50/60 Hertz Models
Without Power Factor Correction
Input Voltage
200
220
230
400
440
460
520
575
Input Amperes At Rated Output*
88
82
77
45
41
38
35
31
Max Recommended Standard Fuse Or Circuit Breaker
Rating In Amperes
Circuit Breaker
1
Time-Delay Fuse
2
125
125
125
70
60
60
50
45
Normal Operating (Fast) Fuse
3
125
125
125
70
60
60
50
45
Min Input Conductor Size In AWG
4
4
6
6
8
8
10
10
10
Max Recommended Input Conductor Length In
Feet (Meters)
167
(51)
137
(42)
153
(47)
305
(93)
369
(112)
281
(86)
352
(107)
439
(134)
Min Grounding Conductor Size In AWG
4
6
6
6
8
10
10
10
10
*
Input amperes at rated output is the amperage draw for that particular input voltage if the machine is run at its rated welding
output (see Section 3-5 for rated welding output).
Reference: 2005 National Electrical Code (NEC)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (fast) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
50/60 Hertz Models
With Power Factor Correction
Input Voltage
200
220
230
400
440
460
520
575
Input Amperes At Rated Output*
60
61
52
34
31
26
26
21
Max Recommended Standard Fuse Or Circuit Breaker
Rating In Amperes
Circuit Breaker
1
Time-Delay Fuse
2
90
90
80
50
45
40
40
30
Normal Operating (Fast) Fuse
3
90
90
80
50
45
40
40
30
Min Input Conductor Size In AWG
4
8
8
8
10
10
10
10
12
Max Recommended Input Conductor Length In
Feet (Meters)
87 (26)
102
(31)
115
(35)
226
(69)
274
(84)
308
(94)
383
(117)
295
(90)
Min Grounding Conductor Size In AWG
4
8
8
8
10
10
10
10
12
*
Input amperes at rated output is the amperage draw for that particular input voltage if the machine is run at its rated welding
output (see Section 3-5 for rated welding output).
Reference: 2005 National Electrical Code (NEC)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (fast) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
Summary of Contents for Syncrowave 250 DX
Page 6: ......
Page 35: ...ENGLISH OM 363 Page 29 Notes...
Page 43: ...ENGLISH OM 363 Page 37 CE Nameplate E 2 1 2 3 4...
Page 47: ...ENGLISH OM 363 Page 41 CE Nameplate 00 4 SEL 1 4 2...
Page 61: ...ENGLISH OM 363 Page 55 231 395 B Figure 7 2 Circuit Diagram For 350 LX Models...
Page 62: ...OM 363 Page 56 225 650 A Figure 7 3 Circuit Diagram For Optional Cooler...
Page 69: ...ENGLISH OM 363 Page 63 Notes...
Page 80: ...Notes...