The MM4130 is used to provide output
voltages or currents proportional to a
thermocouple    (T/C) input signal.   The basic
model MM4130 provides an output
proportional to the millivolt signal from the
thermocouple, while linearized model
MM4130L corrects the thermocouple’s
nonlinearity to provide an output proportional
to temperature. Both models provide cold-
junction compensation via a solid-state
sensor embedded in the thermocouple
terminal strip.

The units utilize a VCO to develop a pulse
train with a duty cycle proportional to the
input. This pulse train is transformer-coupled
to the output stage where the duty cycle data
is converted to a proportional DC output.

Upscale or downscale burnout indication is
provided.   Upscale is standard and is provided
if burnout protection is not specified.

MODEL NUMBERS

These instructions cover the following
model numbers:

MM4130

: Not linearized - output

proportional to input millivolts.

MM4130L

: Linearized - output

proportional to measured
temperature.

Nonisolated thermocouple transmitters are
available as models MM4100 and MM4100L,
described in separate instructions.

OPTIONS

The following options are available on the
MM4130 and MM4130L:

B

Standard burnout protection is
upscale.  Option B  provides
downscale output on burnout.

RT

Reverse-acting transmitter. The
transmitter output  decreases as the

output increases.

U

All circuit boards conformal coated

for

protection against

moisture.

DC Power

Inverter-isolated 12V or 24V

power.

LL

Superior digital output linearization
(MM4130L)

CONTROLS

Two controls, ZERO and SPAN, are
accessible from the top of the module. 
Additional controls inside the module are
factory adjustments which should not be
reset.

MM4130 & MM4130L

ISOLATED

THERMOCOUPLE

INPUT TO DC

TRANSMITTERS

CALIBRATION

The MM4130 and MM4130L are shipped
precalibrated.  If there is a need to
recalibrate, proceed as follows:

Refer to the instrument’s label to determine
your instrument’s supply voltage and input
and output ranges.  Refer to the “Block
Diagram and Pin Connections” for pin
connections.  Connect a precision DC
voltage or current meter to the output.

Connect a calibration input to the terminal
strip on the side of the module.  If a
thermocouple simulator is available, use it
to provide the calibration input, connecting
it to the transmitter with the appropriate
pair of thermocouple wires.  Otherwise,
use copper wires to connect a precision
DC millivolt source to the input.

When a millivolt source and copper wires
are used it will be necessary to measure
and correct for the temperature at the
transmitter’s input connection.  Using
standard tables for your thermocouple,
find the millivolt level corresponding to the
temperature at the input terminals.  Then,
at each calibration temperature, subtract
this voltage from the voltage given by the
thermocouple table. 

 Remember,

calibration accuracy will be no better than
the accuracy of this temperature
measurement.

Using standard thermocouple tables, set
the input to the low end of the input range
and adjust the ZERO control for the low-
end output voltage or current.  Increase
the input to full scale and adjust the SPAN
control for the full-scale output.  Repeat
until both readings are correct.

SPECIFICATIONS

INPUT RANGE

select 

any

 type thermocouple

(min span 5 mV)

OUTPUT RANGE

Voltage

select 

any

 range from

-10 V to +15 V,
10 mA max load (min span 0.2 V)

Current

select 

any

 range from

0 to 50 mA max,

24 V compliance*

(min span 1mA)

18 V compliance for ISO option if

full-scale output >20 mA

OUTPUT RIPPLE 

(peak-to-peak)

<0.1% of span

ACCURACY

±0.1% of span

LINEARITY

Nonlinearized, Output/Input

±0.05% of span

Linearized, Output/Temp

Linearized to match thermocouple’s
millivolt-versus-temperature curve

COMMON MODE REJECTION

120 dB, DC to 60 Hz

ISOLATION

Output/Input

>500 megohms

Breakdown Voltage

>1000 VAC rms

BREAKDOWN, PWR/CIRCUITRY

>1500 VAC rms

OPERATING TEMPERATURE

14°F to 140°F/-10°C to 60°C

TEMPERATURE STABILITY

±(0.02% of span + 1.3µV)/°C max

POWER

2.5 W max
115 VAC ±10%, 50 or 60 Hz
230 VAC ±10%, 50 or 60 Hz

(DC Power Option)

12 VDC (limits 10 VDC to 15 VDC)
24VDC (limits 21 VDC to 32 DC)

Isolation, DC power supply to input
common: 10 megohms

*  Compliance:

The sum of all voltage drops in the output
loop cannot exceed 24 V at rated current
(1200 ohms @ 20 mA).