MM1520, 1521 and 1524

STRAIN GAUGE INPUT

DUAL LIMIT ALARMS

DESCRIPTION

The MM1520 Series Strain Gauge input alarms
monitor a DC input signal from a strain gauge
or bridge and provide dual  setpoint alarm
outputs when the input exceeds the alarm
values.   Each unit can be supplied as a HI/HI,
HI/LO  or LO/LO alarm.   The output relays are
normally de-energized,  and  energize for an
alarm condition.     Two sets of red/green LED
indicate alarm status to make setup easier.
Deadband on both alarms is fixed at 0.25%
of span.

MODEL NUMBERS

These instructions cover the following
setpoint styles:

MM1520

Strain Gauge Input Dual Alarm
 (25-turn screwdriver adj)

MM1521

Strain Gauge Input Dual Alarm

(Single turn dial)

MM1524 

Strain Gauge Input Dual Alarm

(10-turn precision dial)

OPTIONS

These instructions cover the following op-
tions on the MM1520.  Options installed are
listed on the label attached to the side of the
module.

H/H, H/L, L/L

H

 = High alarm. 

Alarm occurs on an increasing signal.

L

 = Low alarm. 

Alarm occurs on a decreasing signal.

NO/NC

Normally open or normally closed
relay contacts:  (see specifications)

R

The Normal condition for the relays is
de-energized.  They energize for alarm
conditions.  Option R (Reverse sense)
reverses this logic (Failsafe). 

U

All circuit boards conformal  coated for
protection against moisture.

CONTROLS

The MM1520, MM1521 and MM1524 mod-
ules contain two setpoint controls, zero and
span adjustments, plus a bridge excitation
voltage adjustment. The setpoint control in
the MM1520 is a 25-turn blind trimpot. 
MM1521 and MM1524  contain 1-turn and 25-
turn respectively.

CALIBRATION

Modules are shipped with ZERO, SPAN and
excitation voltage precalibrated.  The user
needs only adjust the SETPOINT and
DEADBAND for the desired response.

Refer to the instrument's label to determine
your instrument's supply voltage and input
and output ranges.  Refer to the "BLOCK
DIAGRAM AND PIN CONNECTIONS" for pin
connections.

Connect the alarm input to its mating input
device, or to a precision resistance bridge
capable of simulating the input device.

(If it is necessary to recalibrate using
electronic inputs, refer to  the ELECTRONIC
CALIBRATION section.)

To calibrate the alarm setpoints, adjust the
input to the desired alarm 1 setpoint.  Adjust
the SETPOINT 1 control until its LED switches
to red (ccw for a high alarm, cw for low).

Change the input to the desired alarm 2
setpoint and similarly adjust the SETPOINT 2
control.

If there is a need to recalibrate ZERO, SPAN
and excitation voltage, proceed as follows:

Measure the voltage bEXC  &  -EXC
VOLT ADJ control for the desired excitation
voltage.  The voltage is adjustable from 4 to
12 VDC.

Set the input to the low end of the input range.
Turn the SETPOINT 1 control fully ccw.
Adjust the ZERO control until the SETPOINT
1 LED color switches.

Change the input to the high end of the input
range.  Turn the SETPOINT 2  control fully cw.
Adjust the SPAN control until the SETPOINT
2 LED color switches.

Repeat until the ZERO and SPAN settings are
both correct.
After adjusting the ZERO and SPAN controls,
the SETPOINT controls should be reset as
described above.

ELECTRONIC CALIBRATION

If it is necessary to recalibrate using electronic
inputs, proceed as follows:

Measure the voltage bEXC and
-EXC using a precision digital voltmeter.
Connect a calibrated millivolt signal source
between the +SIG and -SIG inputs.  Determine
the input voltage required at each calibration
point.  The required voltage equals the bridge
sensitivity in millivolts per volt, multiplied by
the excitation voltage.  For example, a
sensitivity of 2 mV/V multiplied by 10 V
excitation results in a 20 mV input signal.

RELAY CONTACT PROTECTION

When inductive loads such as motors, relays
or transformers are switched, voltage tran-
sients may be generated which exceed the
ratings of the relay contacts.  The resulting
arcing can quickly destroy the contacts.
(Refer to the SPECIFICATIONS for the relay
contact ratings.)

Surge supression is required across induc-
tive loads to guard against premature relay
failure.  FIGURE  1 illustrates diode surge
supression for a DC load.  The diode's oper-
ating (peak inverse) voltage should exceed
the load's supply voltage by at least 50% and
should have a current rating of at least one
ampere.

FIGURE 2 shows surge suppression for an
AC load, using an MOV (Metal Oxide Varis-
tor) and a capacitor. The breakdown voltage
ratings of both the MOV and the capacitor
must exceed the peak AC

voltage.

With normal sine-wave power, PEAK = 1.414
x RMS voltage.  For 115 VAC  power a 200
volt peak rating is recommended.