MCAC-ATSM-2014-09 R410a tropical air-cooled scroll chiller unit 60Hz
Installation 141
Multi-module combination installation involves special design of the unit, so relevant explanation is
given as follows.
Installation mode of multi-module combination water system pipeline
1) Installation mode I (recommended installation mode)
No.1 unit
No.0 address(main unit)
No.n unit (n≤5)
No.(n-1) unit
No.(3n-4) address
No.(3n-1) address
No.1 address
No.(3n-5) address
No.(3n-2) address
Pump
No.2 address
No.(3n-6) address
No.(3n-3) address
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position
Water flow switch
n : the module quantity, max5
2) Installation mode II
Fig.4-9
(less than 5 modules)
Water flow switch
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position
No.1 unit
No.0 address(main unit)
No.n unit (n≤5)
No.(n-1) unit
No.(3n-4) address
No.(3n-1) address
No.1 address
No.(3n-5) address
No.(3n-2) address
No.2 address
No.(3n-6) address
No.(3n-3) address
Pump
n : the module quantity, max5
Please pay attention to the following items when installing multiple modules:
● Each module corresponds to an address code
which cannot be repeated.
● Main water outlet temperature sensing bulb, target
flow controller and auxiliary electric heater are under
control of the main module.
● One wired controller and one target flow controller
are required and connected on the main module.
● The unit can be started up through the wired
controller only after all addresses are set and the
aforementioned items are determined. The wired
controller is
≤500m away from the outdoor unit.
less than 5 modules
less than 5 modules
Summary of Contents for MGBT-D25W/DN1
Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...
Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...
Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...