MCAC-ATSM-2014-09 R410a tropical air-cooled scroll chiller unit 60Hz
Installation 139
3.3 MGBT-F120W/DN1
Installation of single-module water system pipeline
Total water outlet temperature sensor
Water outlet
Water inlet
Electric control box
Installation of multi-module water system pipeline
1)
Installation mode I (recommended installation mode)
No.1 unit
No.0 address(main unit)
No.n unit (n
≤8)
No.(n-1) unit
No.(2n-3) address
No.(2n-1) address
(less than 8 modules)
No.1 address
No.(2n-4) address
No.(2n-2) address
Pump
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position
Water flow switch
n : the module quantity, max8
Summary of Contents for MGBT-D25W/DN1
Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...
Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...
Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...
Page 50: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 56: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 60: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 88...