R410A Mini Split Chiller 50Hz
MCAC-ATSM-2014-01
28
14. Hydraulic Performance
14.1 Pump head curve(*)
Note:
(*) To obtain the useful head of the installation, subtract the pressure drop of the plate heat exchanger.
14.2 Heat exchanger pressure drop (water side)
Model
Water flow
m
3
/ h
0.8
1.0
1.2
1.4
1.6
1.8
2.0
l/sec
0.222
0.278
0.333
0.389
0.444
0.500
0.556
MGA-D10/N1
Pressure drop
kPa
26
29
33
37
42
46
50
Model
Water flow
m
3
/ h
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
l/sec
0.333
0.389
0.444
0.500
0.556
0.611
0.667
0.722
MGA-D12/N1
Pressure drop
kPa
35
39
44
47
50
53
58
---
MGA-D14/SN1
kPa
28
31
36
40
43
46
50
54
MGA-D16/SN1
kPa
26
29
32
37
41
45
49
52