MCAC-ATSM-2014-01
R410A Mini Split Chiller 50Hz
17
11. Electric Characteristics
Model
Power supply
(V-Ph-Hz)
Rated values(1)
Fuses
Compressors
Fan/fans
Pump
Total
Max.
values(2)
Glass
5×20mm
250V
F.L.I. F.L.A. L.R.A. F.L.I. F.L.A. F.L.I. F.L.A. F.L.I. F.L.A. F.L.I. F.L.A.
Fuse 1
kW
A
A
kW
A
kW
(A)
(kW) (A)
(kW) (A)
MGA-D10/N1
220-240-1-50 5.0
23.2
147
0.3
1.4
0.5
2.2
5.8
26.8
7.54
34.8
10A
MGA-D12/N1
220-240-1-50 5.0
23.2
147
0.37
1.6
0.5
2.2
5.8
27
7.63
35.1
10A
MGA-D14/SN1 380-415-3-50 5.75
9.8
82.4
0.37
1.6
0.5
2.2
6.62
13.6
8.6
17.7
10A
MGA-D16/SN1 380-415-3-50 5.75
9.8
82.4
0.37
1.6
0.5
2.2
6.62
13.6
8.6
17.7
10A
Remark:
F.L.I. :Full load input power.
F.L.A. : Full load ampere.
L.R.A.: Locked rotary ampere.
(1) Outside air temperature 35
℃
-Water temperature at evaporator 12/7
℃
.
(2) Values refer to the lower rated voltage(50Hz). These values are used to judge the protection switch size and the thickness
of the power supply cable.