Service Manual
, 2016-12
29
/
42
故障代码
Fault code
E1
E4
9.3Alarm(None)
9.4Failure code and solutions
Error Code
Failure Type
Solution
E1
Fault of temperature
sensor
Step 1: Check whether the terminal CN4 is well stuck, pull
out the terminal and re-stick it in place
Step 2: Check to see if there’re foreign matters on the
terminal.
Step 3: Inspect the
temperature
sensor whether contact is
bad, and resend contact the fast connector
Step 4: Replace main control board
E4
Fault of F frost sensor
Step 1: Check whether the terminal CN4 is well stuck, pull
out the terminal and re-stick it in place
Step 2: Check to see if there’re foreign matters on the
terminal.
Step 3: Inspect the defrost sensor whether contact is bad,
and resend contact the fast connector
Step 4: Replace main control board
9.5Defrost function
The defrosting of evaporator is activated when the temperature monitored by defrosting sensor is
below setted point., compressor switching off,following the temperature rise, the frost on evaporator
becomes water, and the water flow into the evaporating pan via the draining system, the water in
evaporating pan evaporate away finally.
9.6Compressor fan control (None)
9.7
Self-diagnosis
(None)
Summary of Contents for 22033010000441
Page 5: ...Service Manual 2016 12 5 42 1 Safety Warning Code 1 1Warning for operation safety ...
Page 6: ...Service Manual 2016 12 6 42 ...
Page 7: ...Service Manual 2016 12 7 42 ...
Page 8: ...Service Manual 2016 12 8 42 1 2Safety instruction for refrigerant ...
Page 16: ...Service Manual 2016 12 16 42 UR LC96GE_22033010000441 ...
Page 33: ...Service Manual 2016 12 33 42 11 2No working of compressor ...
Page 35: ...Service Manual 2016 12 35 42 ...